With this parameter, the first reference sensor for heating
circuit backup heating can be selected.
Sensor 1 tank
Arrangement/Heat. circuit/hc/Expert/S1 Tank
adjustment range: 1 ... 10
factory setting: 4
With this parameter, the second reference sensor can be
selected for tank-dependent backup heating.
Sensor 2 tank
Arrangement/Heat. circuit/hc/Expert/S2 tank
adjustment range: 1 ... 10
factory setting: 5
With this parameter, the relay by means of which backup
heating is demanded (DSE or heating circuit module) can
be selected.
Î
Allocate minimum runtime and overrun time of the
relay.
Backup heating demand
Arrangement/Heat. circuit/hc/Expert/rel. ahoff
selection: “DSE”, “HC1”, “HC2”, “HC3”
factory setting: “DSE”
Arrangement/Heat. circuit/hc/Expert/ah-Min.
adjustment range: 0 ... 90 min
factory setting: 0 min
Arrangement/Heat. circuit/hc/Expert/ah
adjustment range: 0 ... 1000 s
factory setting: 0 s
The remote control RTA11-M is used for displacing the
heating curve. It allows manual adjustment of the heating
curve (± 30 °Ra) and is not included in the full kit.
The heating circuit can be switched off manually, if the remo-
te control is set to the position “heating circuit off”. Heating
circuit switched off means that the heating circuit pump is
switched off and the mixing valve closed.
Flow temperature is boosted to maximum for rapid heating
when the remote control it is set to “rapid heating”.
Manual correction (remote control)
Arrangement/Heat. circuit/hc/Expert/man. corr.
selection: “Yes”, “No”
factory setting: “No”
Adjustment channel for allocating the remote control sen-
sor. The factory setting is sensor 8.
Sensor remote control
Arrangement/Heat. circuit/hc/Expert/Sen. remote
adjustment range: 1 ... 10
factory setting: 8
When the chimney sweeper function in the expert menu
(see 4.4) is activated and when the chimney sweeper option
in this menu is activated, the heating circuit opens (mixing
valve opens) and the heating circuit pump is switched on.
The protective function of the heating pump maximum
limitation will still be active.
Chimney sweeper
Arrangement/Heat. circuit/hc/Expert/chimney
selection: “Yes”, “No”
factory setting: “No”