Note:
Select the basic system first, because the sub-
sequent selection of a new system will reset all
other adjustments to the factory settings.
D e lt a S o l
®
E
© RESOL 10306_DeltaSol_E.mon
us.ind
d
|
24
4. Functions and options
4.1 Menu: Solar
Hydronic variation:
Solar/Options/loading
adjustment range: 1 ... 4
factory setting: 1
Many hydronic variations distinguish between pump and
valve control e.g. for multiple tanks. The adjustment has to
be carried out in accordance with the overview of the basic
systems with their hydronic variations (see 3.2). Broadly
speaking, variants with pumps allow speed control, variants
with valves do not and will automatically set the minimum
speed to 100 %.
System:
Solar/Options/System
adjustment range: 1 ... 7
factory setting: 1
Î
Select the appropriate basic system (see 3.2).
Alternatively to the basic system and hydronic variant, one
of the 30 pre-programmed system layouts can be selected.
If a new schematic is selected subsequently, all other adjust-
ments will be reset to the factory settings!
Schematic:
Solar/Options/schematic
adjustment range: 000 ... 030
factory setting: 000