1. Select basic solar system
(
Solar/Options/System
)
2. Select hydronic variation (beginning with system 2)
(
Solar/Options/loading
)
Alternatively to steps 1 and 2:
load system layout (schematic)
(
solar/options/schematic
)
3. Adjust date and time
(
arrangement/adj. values/time
)
4. Activate internal heating circuit module if needed
(
arrangement/heat. circuit/Options/hc
)
5. Adjust parameters for internal heating circuit module
(
Arrangement/heat. circuit/hc/...
)
6. Activate external heating circuit module(s) if needed
(
arrangement/heat. circuit/Option/HC1 (2,3) module
)
7. Adjust parameters for external heating circuit
module(s)
(
arrangement/heat. circuits/Hc1 (2,3) Module/...
)
8. Activate desired functions with relay allocation (if needed)
Bypass
(
Solar/Options/Bypass
)
External heat exchanger
(
Solar/Options/Ext. heat. ex
)
Cooling function
(
Solar/Options/cool. func.
)
Parallel relay
(
Solar/Options/Par.Relay
)
Backup-heating suppression
(
Solar/Options /ah suppress.
)
Protection against Legionnaires‘ disease
(
arrangement/Options/hse
)
Tank loading
(
arrangement/Options /tank load.
)
Error message
(
Expert/message rel.
)
3.4 Adjusting the controller step-by-step
Before adjusting the controller, select the language (
Expert/language/...
).
Points 1. – 3. have to be adjusted for all systems. Points 4. – 18. are optional to suit the system requirements. Points 19.
and 20. should be adjusted before the system is released to the end user.
9. Activate further functions without relay allocation (if
needed):
Evacuated tube collector function
(
Solar/Options/tube col.
)
Collector cooling function
(
Solar/Options/col. cooling
)
Recooling function
(S
olar/Options/Recooling
)
Frost protection
(
Solar/Options/frost. prot.
)
Target temperature
(
Solar/Options/target tem.
)
CS-Bypass
(
Solar/Options/CS-Bypass
)
10. Adjust special parameters of the selected options
(
Solar/adj. values/...
),
(
Solar/Expert/...
) and
(
Arrangement/adj. values/...
)
11. Activate functions of function blocks (if needed)
(
arrangement/Options/...
)
12. Adjust switching conditions for the activated functions
(
Arrangement/adj. values/...
)
13. Activate heat measurement function (if needed)
(
WMZ/Options/...)
14. Adjust special parameters
(
WMZ/WMZ 1/Expert/...
)
15. Deactivate warning message (if needed)
(
Expert/...
)
16. Carry out sensor offset (if needed)
(
Expert/Sensors/...
)
17. Increase minimum speed (if needed)
(
Expert/Relay/...
)
18. Setup and adjust chimney sweeper function (if needed)
(
Expert/chimney/...
)
19. Carry out relay test
(
manual operation/...
)
20. Save adjustments
(
user code/0000
)