background image

Safety Hints 

 
Extensive tests have been conducted on the material, 
functionality and quality of these units before they were 
shipped. These units may only be used in accordance 
with their intended purpose. Hazards may arise if the 
units are used improperly. 

Please make sure to follow these safety instructions. 

Make sure that personnel trained in the operation of 
the chiller check the unit for visible defects on the op-
erating and safety mechanisms each time before 
putting it into operation. 

Before any work on the unit is performed, it must be 
disconnected from the power supply and secured 
against switching on! 

The unit may only be filled up and operated with wa-
ter or a mixture of water and glycol (brine)! 

Ensure that the air intake and outlet openings are al-
ways clear of foreign objects. 

Do not insert any objects into the air intake and outlet 
openings. 

Do not install the unit close to heat sources

.

 

Make sure to maintain the safety zones described 
later in this manual! 

Do not use flammable gases such as spray paint in 
the direct vicinity of the units. 

Make sure that the unit is kept at a safe distance 
from flammable materials. 

Do not operate the unit if the atmosphere is contami-
nated by oil, sulfur or salt. 

If there is a cable remote control installed, make sure 
to protect it against moisture and direct or indirect 
sunlight! 

Unit Description 

 
REMKO chilled water air-conditioning systems consist 
of an outer part ready which is ready to be connected, 
the air-cooled chiller (REMKO RKW INOX) and one or 
more inner units (cold water consumers: REMKO KLT, 
WLT, DKT and FLG). All components required for cool-
ing are located in the outer part. 

A hermetically closed cooling cycle in the chiller cools 
the water (or a brine made of water  and antifreeze) to 
up to 5 °C via a plate heat exchanger. 

A circulation pump integrated either into the unit or in 
the storage module transports the cold water to the in-
ner unit(s). To expand the water volume and extend the 
operating time, there is also a cold water tank with 
safety assembly either in the unit or located in the sepa-
rate storage module. 

In the inner units, the air in the room is guided through 
the heat exchanger of the inner units by means of a 
quiet fan. When the air in the room leaves the unit, it is 
cooled, demoisturized and filtered. The water warms up 
and transports the heat absorbed from the room back to 
the outer part where it is passed along to the cooling cy-
cle and the surroundings. 

The RKW 1000, 1600 and 2600 INOX chillers all have a 
hydraulic system that is ready to be connected with a: 

Buffer tank 

Expansion vessel 

Safety valve 

Flow switch (differential pressure monitor) 

Manometer 

Ventilation 

Ventilation valve  

Drain valve 

The RKW 3600 INOX chiller models and higher can be 
easily equipped with a storage module that has an inte-
grated hydraulic system, even at a later time. 

The system is regulated by means of a self-sufficient 
microprocessor that monitors system safety parameters 
and displays any malfunctions and monitors the set cold 
water temperature. A connection between the chiller 
and the cold water consumers is not required. 

To air condition rooms, an outer part is usually used in 
connection with the appropriate inner units (consumers). 
Here, there are various options available depending on 
how the unit is being used. In addition to standalone 
units, wall and ceiling chests, ceiling cassettes with vari-
ous capacities can also be selected for mounting on in-
termediate walls. 

REMKO chillers are suitable for almost every type of ap-
plication when used with the right consumers if the pri-
ority is cooling according to needs. 

Thanks to modern technology, the chillers require up to 
80 % less coolant than other cooling  and air-
conditioning systems. 

The coolant is only necessary to cool the transport me-
dium (water or brine). In conventional systems, the cool-
ant is also required to transport the heat from the inner 
units (consumers) to the outer part. 

This makes another advantage of the REMKO chillers 
evident; they do not require coolant lines to the inner 
units (cold water consumers). All connection lines are 
designed to be water lines with the correct dimensions 
and heat insulation. 

Ideally, lines of an existing heating network can be inte-
grated into the overall system. 

Proper use 

The outdoor parts have been designed and fitted exclu-
sively for operation with REMKO indoor units belonging 
to the RKV series. 

The manufacturer assumes no liability for damage re-
sulting from non-compliance with manufacturer specifi-
cations and legal requirements, or if modifications are 
made to the units. 

Summary of Contents for RKW 1000 INOX

Page 1: ...REMKO powerful like a bear REMKO RKW 1000 9800 INOX Stainless Steel Chiller Edition GB M11 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...ce Personnel 14 Unit Assembly 14 Storage Modules for RKW 3600 to 9800 I 17 Cable Remote Control 20 Electrical Connection 21 Hydraulic System 24 Initial Operation 25 Environment and Recycling 26 Servic...

Page 4: ...s by means of a quiet fan When the air in the room leaves the unit it is cooled demoisturized and filtered The water warms up and transports the heat absorbed from the room back to the outer part wher...

Page 5: ...arge amounts of dust or aggres sive air Installation and repair work may only be performed by authorised personnel Cleaning and minor maintenance work made only be performed by the operator or an auth...

Page 6: ...on both displays show a value continuous display After the SET button has been pressed the code display parameters starts blinking The displayed values can be increased or de creased using the arrow k...

Page 7: ...g the corresponding programmed output current to the CTK 1 CTK 2 output of the TK 1 TK 2 fan board The fan motor rotation can be controlled by the modulat ing output current Compressor LED This LED is...

Page 8: ...in hours Not installed Operating hours of Compressor 2 23 Fan s Cycle 2 01 02 04 06 Not installed Fans in operation Off not in use Time delay ON OFF 25 Rotations condenser fan s Cycle 2 Not installed...

Page 9: ...i n s t o b l i n k w h e n t h e S E T button is pressed This mode displays the options for changing the parameters to the programmer If one of the arrow keys is now pressed the parameter jumps to t...

Page 10: ...ycle 2 E40 Sensor defective ST 1 incoming water E41 Flow switch differential pressure monitor activated E42 Hardware defective The second parameter level can be programmed to reset the alarms Enter th...

Page 11: ...ture E06 E07 E26 E27 E40 Sensors defective ST1 to ST6 It is the alarm activated when the sensor is replaced Replace defective sensors E41 Flow switch differential pres sure monitor activated Are the f...

Page 12: ...ater chiller inch 1 1 2 2 x 2 Outgoing water chiller inch 1 1 2 2 x 2 Filling connection inch 1 2 Sound pressure level 2 dB A 43 44 49 48 48 53 54 Refrigerant R 407C Cold cycles Compressor type 1 Scro...

Page 13: ...tgoing water inch 1 inside 1 inside 1 inside 2 inside 2 inside 2 x 2 inside 2 x 2 inside M filling connection water inch outside outside outside Fan number mm 450 2 450 2 630 1 630 2 630 2 800 2 800 2...

Page 14: ...room will heat up and the chiller will switch off due to a malfunction This occurs once the room temperature exceeds the upper operating range of the set value of the safety mechanism Minimum distance...

Page 15: ...sorbers in this series These must be connected to statically permissi ble and level building or structural components The locations for attachment described below are for fastening the vibration absor...

Page 16: ...liers must be used to mount the pipe lines on the RKW so as not to create any strain on the pipe lines in the inside of the unit If the chiller is only initially operated with a single part of the ove...

Page 17: ...ge module 3 for RKW 8000 and 9800 INOX 2 x 216 l tanks safety component 3 kPa and MAG without pump Ref No 1611545 4 Storage module 4 for RKW 8000 and 9800 INOX 2 x 216 l tanks safety component 3 kPa a...

Page 18: ...a 5 8 6 10 8 11 10 11 15 13 Available external pressure differential kPa 92 89 59 66 47 32 Electrical connection V 3 400 3 400 3 400 Power Current consumption kW A 0 55 1 44 0 55 1 44 0 75 1 86 1 1 2...

Page 19: ...ption max 1 44 A 1 44 A 1 86 A 400 V 50 Hz 3 N PE Characteristic curve of the pump RKW 3600 4500 INOX storage module 2 Characteristic curve of the pump RKW 8000 9800 INOX storage module 4 Characterist...

Page 20: ...contact with drinking water or food antifreeze L is to be given preference because it contains the physiologically harmless substance 1 2 propylene glycol The data provided in the table refers to anti...

Page 21: ...AT 9 Differential pressure monitor Neutral contact 15 17 AT 7 Heating cooling removed Neutral contact 15 18 closed AT 10 On Off remote control contact for heating pump Neutral contact 19 20 RL 1 Glob...

Page 22: ...Verfl ssiger fan 1 Potentialfreier Kontakt for regulating cool ing EXTERNAL Flow switch EXTERNAL Phase sequence relay Terminal strip M1 Terminal strip M2 Compressor motor Relay compressor ST 1 Tempera...

Page 23: ...4 L1 N L1 12V 12V N Pri 230V CH DIN regulation C2 DIN regulation Additional module for the remote control Transformer 220 12 V in the switch box RKW Operating module Maximum line length 50 meter Assem...

Page 24: ...1 15 13 3 1 2 12 17 14 10 16 18 9 6 5 4 7 8 15 13 3 Hydraulic Diagram RKW 8000 9800 INOX 1 2 12 17 14 1 16 18 9 6 5 4 7 8 1 15 P 10 19 Terminal strip M1 Condenser fan 1 and 2 Klemmleiste M2 Compressor...

Page 25: ...is correct The electrical lines of the system must be checked that they are attached properly to the terminal strips Prior to operation all screws in the water system must be checked to ensure that th...

Page 26: ...then select a higher drainage temperature 17 The supply temperature is approx 5 Kelvin under the drainage temperature for the rated flow rate 18 If the supply temperature is below the factory setting...

Page 27: ......

Page 28: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Reviews: