background image

20 

Electrical connection of the cable remote control 

The remote control comes with an operating module 
TS-W, the additional regulation module CS-DIN/TTL  
and an interface line. 

Cable Remote Control 

 

The cable remote control can be purchased as an ac-
cessory. It is used to query and program the chiller from 
a remote location. 

In the factory, all models are programmed using the re-
mote control. 

Install the remote control as follows: 

1) Place the two, two wire connection lines between the 

location where the remote control is to be assembled 
and the switch box of the chiller. The minimum 
cross-section is Cu 1.5 mm². The max. current may 
not fall below 2 %. 

2) Remove the assembly back panel of the operating 

module and attach it to the setup location. 

3) Clamp the lines to the terminal strips of the elec-

tronic board and make sure that the polarity is cor-
rect. Lock the operating module into place in the as-
sembly back panel. 

4) Insert the additional module into the switch box of 

the chiller. 

5) Clamp the lines to the terminal strips of the previ-

ously mounted additional regulation module in the 
switch box of the chiller. 

6) Using the interface line, you can connect the addi-

tional regulation module and the CH–DIN regulation. 

7) Test the function of the remote control. 

Percent-

age of 

ethylene 

glycol 

Correction factors when using a brine 

made of ethylene glycol * and water 

Cooling 

capacity 

Power 

consump-

tion 

Flow rate 

Pressure 

loss 

Vol. % 

°C 

K

K

PE 

K

K

20 

-11 

0.96 

0.995 

1.04 

1.19 

34 

-20 

0.95 

0.990 

1.09 

1.35 

40 

-25 

0.925 

0.985 

1.105 

1.51 

Anti-

freeze 

*   We recommend an ethylene glycol with inhibitors as 

corrosion protection, e.g. antifreeze N or L. 

Where the heat medium comes into contact with 
drinking water or food, antifreeze L is to be given 
preference because it contains the physiologically 
harmless substance 1.2 propylene glycol. 

The data provided in the table refers to antifreeze N. 
Antifreeze L has other correction factors and thus a 
different pressure loss! 

Antifreeze to prevent freezing 

During cold seasons of the year, it is possible that the 
water in the chiller will freeze at temperatures below 0°C 
which can cause damage, for example, to the plate heat 
exchanger. The same applies to installed connection 
lines and system parts in rooms not susceptible to frost. 

For this reason, we recommend mixing the water with 
an adequate amount of antifreeze (e.g. antifreeze N). 

If brine (a mixture of water and frost protection) is not 
used in the hydraulic cycle, the  water is to be drained 
from the system parts in areas susceptible to frost dur-
ing non-operation in the winter. 

Appropriate shut-off and drainage mechanisms are to 
be used. The amount of water drained out must be re-
filled before the next cooling season begins. 

If the chiller is to be used throughout the whole year, e.
g. to air-condition a computer room) the hydraulic cycle 
must be operated with brine. 

When using brine, you must make sure that the pres-
sure loss increases as a result of the changing density 
in the hydraulic cycle. Whether or not to use brine must 
be considered when the hydraulic cycle is being set up. 

The variable technical data can be found in the table be-
low: 

The operating module is to be mounted in the desired 
location. The operating module is connected to the 
RKW with two, two-wire lines with a maximum length of 
50 m. One line is used to transfer data and the other to 
supply the current 12 V~ of the operating module. It is 
not necessary to use an additional transformer. 

The programmed data is transferred to the CH– DIN 
regulation by an interface line. 

CS-DIN/TTL 

TS-W 

Summary of Contents for RKW 1000 INOX

Page 1: ...REMKO powerful like a bear REMKO RKW 1000 9800 INOX Stainless Steel Chiller Edition GB M11 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...ce Personnel 14 Unit Assembly 14 Storage Modules for RKW 3600 to 9800 I 17 Cable Remote Control 20 Electrical Connection 21 Hydraulic System 24 Initial Operation 25 Environment and Recycling 26 Servic...

Page 4: ...s by means of a quiet fan When the air in the room leaves the unit it is cooled demoisturized and filtered The water warms up and transports the heat absorbed from the room back to the outer part wher...

Page 5: ...arge amounts of dust or aggres sive air Installation and repair work may only be performed by authorised personnel Cleaning and minor maintenance work made only be performed by the operator or an auth...

Page 6: ...on both displays show a value continuous display After the SET button has been pressed the code display parameters starts blinking The displayed values can be increased or de creased using the arrow k...

Page 7: ...g the corresponding programmed output current to the CTK 1 CTK 2 output of the TK 1 TK 2 fan board The fan motor rotation can be controlled by the modulat ing output current Compressor LED This LED is...

Page 8: ...in hours Not installed Operating hours of Compressor 2 23 Fan s Cycle 2 01 02 04 06 Not installed Fans in operation Off not in use Time delay ON OFF 25 Rotations condenser fan s Cycle 2 Not installed...

Page 9: ...i n s t o b l i n k w h e n t h e S E T button is pressed This mode displays the options for changing the parameters to the programmer If one of the arrow keys is now pressed the parameter jumps to t...

Page 10: ...ycle 2 E40 Sensor defective ST 1 incoming water E41 Flow switch differential pressure monitor activated E42 Hardware defective The second parameter level can be programmed to reset the alarms Enter th...

Page 11: ...ture E06 E07 E26 E27 E40 Sensors defective ST1 to ST6 It is the alarm activated when the sensor is replaced Replace defective sensors E41 Flow switch differential pres sure monitor activated Are the f...

Page 12: ...ater chiller inch 1 1 2 2 x 2 Outgoing water chiller inch 1 1 2 2 x 2 Filling connection inch 1 2 Sound pressure level 2 dB A 43 44 49 48 48 53 54 Refrigerant R 407C Cold cycles Compressor type 1 Scro...

Page 13: ...tgoing water inch 1 inside 1 inside 1 inside 2 inside 2 inside 2 x 2 inside 2 x 2 inside M filling connection water inch outside outside outside Fan number mm 450 2 450 2 630 1 630 2 630 2 800 2 800 2...

Page 14: ...room will heat up and the chiller will switch off due to a malfunction This occurs once the room temperature exceeds the upper operating range of the set value of the safety mechanism Minimum distance...

Page 15: ...sorbers in this series These must be connected to statically permissi ble and level building or structural components The locations for attachment described below are for fastening the vibration absor...

Page 16: ...liers must be used to mount the pipe lines on the RKW so as not to create any strain on the pipe lines in the inside of the unit If the chiller is only initially operated with a single part of the ove...

Page 17: ...ge module 3 for RKW 8000 and 9800 INOX 2 x 216 l tanks safety component 3 kPa and MAG without pump Ref No 1611545 4 Storage module 4 for RKW 8000 and 9800 INOX 2 x 216 l tanks safety component 3 kPa a...

Page 18: ...a 5 8 6 10 8 11 10 11 15 13 Available external pressure differential kPa 92 89 59 66 47 32 Electrical connection V 3 400 3 400 3 400 Power Current consumption kW A 0 55 1 44 0 55 1 44 0 75 1 86 1 1 2...

Page 19: ...ption max 1 44 A 1 44 A 1 86 A 400 V 50 Hz 3 N PE Characteristic curve of the pump RKW 3600 4500 INOX storage module 2 Characteristic curve of the pump RKW 8000 9800 INOX storage module 4 Characterist...

Page 20: ...contact with drinking water or food antifreeze L is to be given preference because it contains the physiologically harmless substance 1 2 propylene glycol The data provided in the table refers to anti...

Page 21: ...AT 9 Differential pressure monitor Neutral contact 15 17 AT 7 Heating cooling removed Neutral contact 15 18 closed AT 10 On Off remote control contact for heating pump Neutral contact 19 20 RL 1 Glob...

Page 22: ...Verfl ssiger fan 1 Potentialfreier Kontakt for regulating cool ing EXTERNAL Flow switch EXTERNAL Phase sequence relay Terminal strip M1 Terminal strip M2 Compressor motor Relay compressor ST 1 Tempera...

Page 23: ...4 L1 N L1 12V 12V N Pri 230V CH DIN regulation C2 DIN regulation Additional module for the remote control Transformer 220 12 V in the switch box RKW Operating module Maximum line length 50 meter Assem...

Page 24: ...1 15 13 3 1 2 12 17 14 10 16 18 9 6 5 4 7 8 15 13 3 Hydraulic Diagram RKW 8000 9800 INOX 1 2 12 17 14 1 16 18 9 6 5 4 7 8 1 15 P 10 19 Terminal strip M1 Condenser fan 1 and 2 Klemmleiste M2 Compressor...

Page 25: ...is correct The electrical lines of the system must be checked that they are attached properly to the terminal strips Prior to operation all screws in the water system must be checked to ensure that th...

Page 26: ...then select a higher drainage temperature 17 The supply temperature is approx 5 Kelvin under the drainage temperature for the rated flow rate 18 If the supply temperature is below the factory setting...

Page 27: ......

Page 28: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Reviews: