Controls (cont.)

Each unit shall incorporate an automatic indoor coil frost
control to extend compressor life by limiting operation in
low ambient conditions.

In case of power failure, each unit will randomly restart
when power resumes to avoid overloading and power
surging of the electrical circuits. Also, upon restart, the
unit shall retain its last control setting.

An Owner/Facility manager selectable fan cycle switch
shall be incorporated to allow either continuous or cycle
operation of indoor fan.

Room freeze protection shall be incorporated to safe-
guard against freezing indoor temperatures and shall be
Owner/Facility Manager activated/deactivated. When
activated, if the indoor temperature drops to 40° F,
regardless of the control setting the electric heater and
indoor fan will automatically energize to prevent further
room temperature decline.

Outside Air Louvers

Outside air louvers shall be (stamped) (extruded archi-
tectural) anodized aluminum finished natural (stamped
louvers shall be heavy gauge anodized aluminum of no
less than 16 gauge). Extruded architectural louvers are
also available with baked enamel to match color chip by
others. Louvers by others must be approved by the heat-
ing/cooling chassis manufacturer as to adequate free
area and air circulation requirements.

Electrical Subbase

As specified and shown on plans, a 3" or 4" high electri-
cal subbase shall be furnished. Electrical subbase shall
be ETL and CETL listed and constructed of heavy gauge
steel and finished with epoxy based powder paint to
resist corrosion. Optional fused disconnects are also

available. To ease field installation, subbase must have
adjustable side channels with predrilled adjusting holes
and score lines. Additionally, subbase shall have
adjustable leveling legs each with 1" adjustment.

Front Panel

Each heating/cooling chassis shall come complete with a
decorative front panel. Front panel shall be designed
with a contoured top to facilitate airflow into the room.
Additionally, it shall be designed to wrap-around the
heating/cooling chassis and constructed of impact resist-
ant polymer. The color of the front panel shall be Antique
Ivory as to match that of the wall sleeve. The airflow dis-
charge grille shall be an integral part of the front panel
and shall be made of the same impact resistant polymer
material as the front panel. The discharge grille shall
consist of a single section and be designed to be two-
position reversible to customize the direction of airflow
out of the unit. Room side return air shall enter the heat-
ing/ cooling chassis through the louvered front panel.

Filtration

Room side return air shall be completely filtered through
permanent, washable polypropylene mesh filters. Foam
type filters are not acceptable. Filters shall be designed
for easy access without removing the front panel.

Wall Sleeve

The wall sleeve shall be entirely constructed of A-60 gal-
vaneal, phosphatized, 18-gauge steel. It shall be finished
with polyurethane based powder paint to provide maxi-
mum corrosion protection. Additionally, the interior top
and side surfaces shall be insulated. Wall sleeves with
ordinary enamel finish or those made from polymeric
material are not acceptable. Wall sleeves shall have fac-
tory provisions for use of appropriate fastening devices
to secure sleeve to the wall through the sides.

Summary of Contents for Amana PTC

Page 1: ...Packaged Terminal Air Conditioners and Heat Pumps Architects and Engineers Manual...

Page 2: ...p Front Cleanable Filter Standard Standard Standard Standard Standard Standard Standard Standard Automatic Indoor Frost Control Standard Standard Standard Standard Standard Option Corrosion Treated Ch...

Page 3: ...llation page 14 Drain Kit Installation page 15 Unit Dimensions page 16 Table of Contents Bi Directional Discharge Grille High Efficiency Refrigeration Coils Chassis Fits Any Standard 16 H x 42 W x 133...

Page 4: ...Costs The overall system design is greatly simplified allowing designers to devote more time to other areas and reducing overall costs Architectural Design Freedom Eliminates the need for large mecha...

Page 5: ...ditional labor required to enable the damper Extra Humidity Control Remington is the only AC manufacturer to offer the Cool Dry Dehumidification Mode standard on all units The system is designed to pr...

Page 6: ...H x 42 W x 133 4 D wall opening Remington conditioners are compatible with most existing wall thermostats and remote control interfaces for added savings on installation labor and costs Insulated wall...

Page 7: ...for guest comfort and energy savings Automatically controls unit shut off after a specified time 1 to 15 hours Adjustable minimum and maximum room temperature set points Allows wireless remote contro...

Page 8: ...ectly connected to a two speed motor All fans shall be statically and dynamically bal anced to provide for quiet and smooth operation During the cooling cycle the compressor and both fan motors shall...

Page 9: ...ours This will automatically compensate for the cold or warm radiation effect felt from the mass in the walls floor and furnishings until they normalize The 2 F offset is maintained for the first cycl...

Page 10: ...disconnects are also available To ease field installation subbase must have adjustable side channels with predrilled adjusting holes and score lines Additionally subbase shall have adjustable levelin...

Page 11: ...65V models and is optional for 208V 230V models Figure 1 shows the subbase and dimensions Power Supply Wiring All wiring must be done in accordance with all local and National Electrical Code requirem...

Page 12: ...select the number of hours 1 15 after which the unit will turn off To turn the unit on preset the unit to the desired mode and temperature and turn it off Press the TIMER key repeatedly to select the...

Page 13: ...ll sleeve applications 111 2 D that do not conform to industry standard depth 133 4 D Drain Kits Internal or external mounted drain kits Pre drilled wall sleeve simplifies drain kit installation Subba...

Page 14: ...Amps 18 5 20 7 18 0 18 5 20 7 18 5 Capacity Btuh 7 100 7 400 7 300 8 900 8 900 8 900 11 000 11 400 11 400 14 000 14 500 14 400 Cooling EER 11 6 11 5 10 7 10 6 10 4 10 4 10 0 9 9 10 1 9 3 9 3 9 2 Full...

Page 15: ...Page 13 Wiring Diagrams Model PTAC 07B 09B 12B 15B...

Page 16: ...wall and panel wall applications for positive anchoring to the wall For thicker walls wall sleeve extensions are available from your local Remington representative Air splitters must be included in w...

Page 17: ...wall sleeve has been installed Note When using the ex ternal drain kit the sleeve must be flush or beyond the out side finished wall do not recess Install the external drain kit as follows 1 Assemble...

Page 18: ...available in 3 or 4 height with depth adjustable from 43 8 to 133 4 Unit pictured with subbase installed but can also be floor mounted without subbase for 208V 230V applications Side View Top View Fro...

Page 19: ...m Blue MGN Medium Green SPECIAL COLOR We can match your color A color chip or sample should be sent to our Customer Service Department A sample chip will be returned to you for your approval Please co...

Page 20: ......

Reviews: