Supplied By www.heating spares.co Tel. 0161 620 6677
22
Remeha Gas 360 S
20/07/05 - 300005180-001-A
Incidents and solutions
Symptoms
Probable causes
Solution
The heater does not start
and the safety box is not
affected (red alarm
indicator off)
- The heater thermostat is
requiring heat
- Create a demand by moving the heater thermostat or the setting level
(option).
- Setting (option) is not requiring
heat.
- The safety thermostat has been
triggered after overheating.
- Solve the cause of overheating and reset the safety thermostat.
- No current
- Place the Stop/Start switch on "On"
The burner does not
ignite and the safety box
is not affected (red alarm
indicator off)
- On safety because of a lack of
gas
- Purge the gas supply pipe then reset the heater using the panel reset
button
- Faulty gas valve (1st stage)
- Check the gas valve and replace if necessary.
- No spark from the electrode
- Check the electric cable connection to the safety box and the electrode
- Commissioning by switching off
the draught diverter thermostat
- Check for adequate draw on the chimney connection. Press the reset
button on the safety control box.
- No ionisation current
- Check the ionisation probe and earth wire connection.
- Check the position of the ionisation probe and the flame diffuser in the
ignition burner
- Blocked filter or ignition burner
injector
- Clean the filter and the ignition burner injector
The burner ignites and
the safety box goes into
standby (burner cut and
the alarm indicator
flashes)
- Anti-blowback thermostat cut
- Check for adequate draw on the chimney connection. Press the reset
button on the safety control box.
- Check that the draught diverter thermostat is in good condition. Press the
reset button on the safety control box.
Please note the seriousness of unplanned intervention on the
combustion product evacuation checking device : evacuation faults must
be solved by improving the draught in the chimney.
In the event of a thermostat fault, it must be replaced by a part stated on
our "Spare parts list". It position must not be changed, it is defined by the
2 fixing brushes which are positioned in 2 holes in the anti-blowback
device. The thermostat must not be placed out of service.
The burner ignites and
the safety box is affected
(alarm indicator on)
- Inversion of the phase and
neutral wires on the heater's
command panel
- Connect the phase to terminal 1 and neutral to 2.
The burner ignites but
with reduced power
- Upstream pressure too weak
- Check gas supply
- Dirty filter
- Clean the filter
- Gas block faulty
- Change them
- Nozzles and/or diaphragms
unsuitable (See Table "Pressure
setting and marking of calibrated
injectors")
- Check them
- Faulty gas valve
- Check gas valve and replace if necessary
- Injectors too small
- Check them (See Table "Pressure setting and marking of calibrated
injectors")
Dirty cast iron body
(hearth)
- Upstream pressure too high
- Check gas supply
- Dirty burner
- Clean the burner
- Insufficient or poorly placed air
supply
- Enlarge air supply, smoothen airation holes
- Faulty gas valve
- Check gas valve and replace if necessary