20/07/05 - 300005180-001-A
Noisy heater
- Poor purge
- Purge correctly
- Body has scale
- Descale the heating circuit
- Unsuitable injectors (Whistling) - Check injectors
Heater too hot or too cold
for requirements
- 3 position switch on position
!
- Check the position of the 3 position switch
- Wrong setting for the heater
thermostat
- Set the heater thermostat if the heater has SV-matic setting or an ambient
thermostat
Flame returns
- Injectors too large
- Pressure too weak
- Check pressure injectors
Whistling
- Injectors too small
- Pressure too high
- Check pressure injectors
Symptoms
Probable causes
Solution