EĆ1
Appendix E
Run Time LED Error Codes
WARNING
ONLY QUALIFIED PERSONNEL FAMILIAR WITH THE CONSTRUCTION AND
OPERATION OF THE CONTROLLED EQUIPMENT SHOULD INSTALL, ADJUST,
OPERATE, OR SERVICE THIS EQUIPMENT. READ AND UNDERSTAND THIS
MANUAL AND OTHER MANUALS APPLICABLE TO YOUR INSTALLATION.
FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY INJURY.
WARNING
INSERTING OR REMOVING THIS MODULE OR ITS CONNECTING CABLES MAY
RESULT IN UNEXPECTED MACHINE MOTION. POWER TO THE MACHINE
SHOULD BE TURNED OFF BEFORE INSERTING OR REMOVING THE MODULE
OR ITS CONNECTING CABLES. FAILURE TO OBSERVE THESE PRECAUTIONS
COULD RESULT IN BODILY INJURY.
STOP ALL Error Codes
Thefollowing hardwareand softwareerror codes causeall tasks running in the
rack to stop.
10
Event count underflow
Ć too many WAITs (max. 32768)
Ć not enough SETs (BASIC tasks)
11
Event count overflow
Ć too many SETs (max. 32767)
Ć not enough WAITs (BASIC tasks)
12
Hardware event timeĆout
Ć interrupt time exceeded programmed timeĆout
limit in a Control Block task
13
Runbaseboot error
Ć a check on therunbasefailed
14
Processor overlap limit exceeded
Ć ran out of processing capacity (time)
15
External watchdog timeĆout detected
Ć another processor in the same rack stopped
17
Address error detected
Ć caused by a read/write to an invalid address
18
Spurious interrupt or hardware failure
19
Power failure detected
1A
Watchdog on this Processor failed
1b
Hardware event count limit exceeded
Ć too many interrupts set without being
acknowledged
Ć program too long
Ć collective scans too fast
1C
Illegal instruction detected
Ć runbasesoftwarefault
Ć bad Processor module
Ć bad EPROMs