background image

6.

Model F1 Res 44 & 58 HSW

Model F1 Res 44 & 58 Recessed HSW/F2

F2 escutcheon,

1/2” (13mm) adjustment

Technical Data: F1Res 44 HSW & HSW/F2

Thread

Size

Nominal

Ori

fi

 ce

Inch (mm)

Sprinkler

Temp. Rating

Max.

Pressure

psi (bar)

Max.

Ambient 

Temp.

K

Factor

Sprinkler

Length

Inch (mm)

°F

°C

°F

°C

½” NPT 

(R½)

3

/

8

” (10)

155
175

68
79

175 (12)

100
150

38
66

4.4

2.45 (62)

Escutcheon, F2, Data:

Type

Adjustment 

Inch (mm)

Face of Fitting 

to  wall

Inch (mm)

F2

1

/

2

 (13)

3

/

16

 - 

11

/

16

(4.7 - 17.4)

Max. 

Sprinkler Spacing

ft (m)

“A”

Ceiling to 

De

fl

 ector

Inch (mm)

Sprinkler Temp. 

Rating
°F (°C)

Flow

gpm (Lpm)

Pressure

psi (bar)

Sprinkler

Identi

fi

 cation

Number (SIN)

12 x 12 (3,6 x 3,6)

 4 - 6

(101 - 152)

155 (68)

175 (79)

12 (45,4)

7.5 (0,52)

R3531

14 x 14 (4,3 x 4,3)

155 (68)

175 (79)

14 (53,0)

10.2 (0,71)

16 x 16 (4,9 x 4,9)

155 (68)

175 (79)

16 (60,6)

13.3 (0,92)

16 x 18 (4,9 x 5,5)

155 (68)

175 (79)

18 (68,1)

16.8 (1,16)

18 x 18 (5,5 x 5,5)

155 (68)

175 (79)

19 (72,0)

18.7 (1,29)

16 x 20 (4,9 x 6,1)

155 (68)

175 (79)

23 (87,1)

27.4 (1,89)

12 x 12 (3,6 x 3,6)

 6 - 12

(152 - 305)

155 (68)

175 (79)

14 (53,0)

10.2 (0,71)

14 x 14 (4,3 x 4,3)

155 (68)

175 (79)

16 (60,6)

13.3 (0,92)

16 x 16 (4,9 x 4,9)

155 (68)

175 (79)

17 (64,4)

15.0 (1,04)

16 x 18 (4,9 x 5,5)

155 (68)

175 (79)

20 (75,7)

20.7 (1,43)

16 x 20 (4,9 x 6,1)

155 (68)

175 (79)

23 (87,1)

27.4 (1,89)

Fig. 5

Summary of Contents for Pantman F1

Page 1: ...rofile decorative de sign The F1 Res Horizontal Sidewall sprinklers Figs 5 6 7 are equally attractive when above ceiling piping can not be used 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 1...

Page 2: ...h for installing Models F1 Res Recessed Pendent CCP SWC sprinklers use only the Model GFR2 sprinkler wrench for installing Model F1 Res Recessed HSW sprin klers use only the Model GFR2 Sprinkler Wrenc...

Page 3: ...5 5 x 5 5 17 64 3 12 0 0 83 20 x 20 6 1 x 6 1 20 75 7 16 7 1 14 Deflector to ceiling Maximum 4 100mm to 8 203mm Max Sprinkler Spacing ft m Flow gpm Lpm Pressure psi bar Sprinkler Identification Numbe...

Page 4: ...Inch mm Sprinkler Temp Rating Max Pressure psi bar Max Ambient Temp K Factor Sprinkler Length Inch mm F C F C 3 4 NPT R 17 32 13 5 155 175 68 79 175 12 100 150 38 66 7 6 2 25 57 Max Sprinkler Spacing...

Page 5: ...tion A Inch mm Max Recessed 7 16 11 Min Recessed 15 16 24 Note Sprinklers shown in Fig 3 and Fig 4 are not suitable for installation in ceil ings which have positive pressure in the space above Techni...

Page 6: ...ch mm Sprinkler Temp Rating F C Flow gpm Lpm Pressure psi bar Sprinkler Identification Number SIN 12 x 12 3 6 x 3 6 4 6 101 152 155 68 175 79 12 45 4 7 5 0 52 R3531 14 x 14 4 3 x 4 3 155 68 175 79 14...

Page 7: ...31 14 x 14 4 3 x 4 3 14 53 0 10 2 0 71 16 x 16 4 9 x 4 9 17 64 3 15 0 1 1 16 x 18 4 9 x 5 5 19 71 8 18 7 1 13 16 x 20 4 9 x 6 1 23 87 1 27 4 1 89 12 x 12 3 6 x 3 6 6 12 152 305 14 52 9 10 2 0 71 14 x...

Page 8: ...ndard finish Bronze Chrome plated White Polyester Special finish specify Recessed escutcheon assembly shall be a steel two piece escutcheon with adjustment Model F2 with adjustment Model F1 of push on...

Page 9: ...er Spe cial finish specify Recessed escutcheon assembly shall be a steel two piece escutcheon with adjust ment Model F2 with adjustment Model F1 of push on and thread off design with adjustment Mod el...

Page 10: ...hroughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dr...