Sprinklers should be inspected quarterly, and the sprinkler sys-
tem maintained in accordance with NFPA 25, 13, 13D, and 13R.  
Do not clean sprinkler with soap and water, Ammonia or any oth-
er cleaning fluids. Remove dust by using a soft brush or gentle 
vacuuming. Remove any sprinkler which has been painted (oth-
er than factory applied) or damaged in any way. A stock of spare 
sprinklers should be maintained to allow quick replacement of 
damaged or operated sprinklers. Prior to installation, sprinklers 
should remain in the original cartons and packaging until used. 
This will minimize the potential for damage to sprinklers that could 
cause improper operation or non-operation.

Model F1 Res 30, 49 & 58 Pendent
Sprinkler Speci

fi

 cations

Sprinklers shall be [cULus Listed] [New York City MEA Ap-

proved (258-93-E)] low flow residential pendent sprinklers en-
gineered to provide a minimum design density of 0.05 gpm/ft

2

 

over the listed coverage area.   Listed flows as specified by the 
manufacturer’s technical data sheets are to be used.  Residential 
sprinklers shall be installed in conformance with the manufac-
turer’s installation guidelines and the applicable installation stan-
dard.  Where pendent residential sprinklers are installed under 
sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers 
shall be listed for such use.  Deflector-to-ceiling distance listing 
shall be 1” to 8” maximum. Sprinkler frame and deflector shall 
be of bronze frame construction having a ½” NPT thread.  Water 
seal assembly shall consist of a Teflon-coated Belleville spring 
washer with top-loaded extruded or cold head cup with 3 mm 
glass bulb containing no plastic parts, and having a temperature 
rating of [155°F (68°C)] [175°F (79°C)].  Sprinklers shall have a 
nominal K-factor of 3.0, 4.9 and 5.8.  Standard finish: [Bronze] 
[Chrome-plated] [White Polyester] [Special finish– specify]. Resi-
dential pendent sprinklers shall be Reliable Model F1 Res 30, 49 
& 58, SIN R3511, R3516 & R3513 (Bulletin 135).

Model F1 Res 49 & 58 Recessed Pendent/F1, 
Model F1 Res 30, 49 & 58 Recessed Pendent/F2, 
Model F1 Res 30, 49 & 58 Recessed Pendent/FP

Sprinklers shall be [cULus Listed] [New York City MEA Ap-

proved (258-93-E)] low flow residential recessed pendent 
sprinklers engineered to provide a minimum design density 
of 0.05 gpm/ft

2

 over the listed coverage area.   Listed flows as 

specified by the manufacturer’s technical data sheets are to be 
used.  Residential sprinklers shall be installed in conformance 
with the manufacturer’s installation guidelines and the applica-
ble installation standard.  Where pendent residential sprinklers 
are installed under sloped ceilings having a pitch from [4/12] 
to [8/12], the sprinklers shall be listed for such use.  Deflector-
to-ceiling distance listing shall be 1” to 8” maximum. Sprinkler 
frame and deflector shall be of bronze frame construction hav-
ing a ½” NPT thread.  Water seal assembly shall consist of a 
Teflon-coated Belleville spring washer with top-loaded extruded 
or cold head cup with 3 mm glass bulb containing no plastic 
parts, and having a temperature rating of [155°F (68°C)] [175°F 
(79°C)].  Sprinklers shall have a nominal K-factor of 3.0, 4.9 & 
5.8.  Standard finish: [Bronze] [Chrome-plated] [White Polyester] 
[Special finish– specify].  Recessed escutcheon assembly shall 

be a steel, two-piece escutcheon [with ½” adjustment (Model 
F2)] [with ¾” adjustment (Model F1)] [of push-on and thread off 
design with ½” adjustment (Model FP)]. Standard finish shall be 
[brass][bright chrome] [white painted].  Residential recessed 
pendent sprinklers shall be Reliable [Model F1 Res 30, 49 & 58 
Recessed Pendent/F1] [Model F1 Res 30, 49 & 58 Recessed 
Pendent/F2] [Model F1 Res 30, 49 & 58 Recessed Pendent/FP] 
SIN R3511, R3516 & R3513 (Bulletin 135).

Model F1 Res 30, 49 & 58 CCP Pendent (Concealed)

Sprinklers shall be [cULus Listed] [New York City MEA Ap-

proved (258-93-E)] low flow residential concealed sprinklers en-
gineered to provide a minimum design density of 0.05 gpm/ft

2

 

over the listed coverage area.   Listed flows as specified by the 
manufacturer’s technical data sheets are to be used. Residential 
sprinklers shall be installed in conformance with the manufac-
turer’s installation guidelines and the applicable installation stan-
dard. Where pendent residential sprinklers are installed under 
sloped ceilings having a pitch from [4/12] to [8/12], the sprinklers 
shall be listed for such use. Sprinkler frame and deflector shall 
be of bronze frame construction having a ½” NPT thread.  Water 
seal assembly shall consist of a Teflon-coated Belleville spring 
washer with top-loaded extruded or cold head cup with 3 mm 
glass bulb containing no plastic parts, and having a temperature 
rating of 155°F (68°C).  Cover plate assembly shall consist of a 
brass cover plate and copper alloy retainer flange.  Method of 
attaching the cover plate to the sprinkler cup shall be a push-
on and thread-off design allowing a ½” cover plate adjustment.  
Cover plate temperature rating shall be 135°F (57°C).  A plastic 
protective cap shall be provided and factory installed inside the 
sprinkler cup to protect the sprinkler from damage, which could 
occur during construction before the cover plate is installed. 
Standard cover plate finish: [White] [Custom Color– specify]. ]. 
Concealed pendent sprinklers shall be Reliable Model F1 Res 
30, 49 & 58 CCP, SIN R3511, R3516 & R3513 (Bulletin 135).

Model F1 Res 44 Horizontal Sidewall
Residential Sprinkler Speci

fi

 cations

Sprinklers shall be [cULus Listed] [New York City MEA Ap-

proved (258-93-E)] low flow residential horizontal sidewall sprin-
klers engineered to provide a minimum design density of 0.05 
gpm/ft

2

 over the listed coverage area.   Listed flows as speci-

fied by the manufacturer’s technical data sheets are to be used.  
Residential sprinklers shall be installed in conformance with the 
manufacturer’s installation guidelines and the applicable instal-
lation standard.  Where horizontal sidewall residential sprinklers 
are installed under sloped ceilings having a pitch from [4/12] to 
[8/12], the sprinklers shall be listed for such use. Sprinkler frame 
and deflector shall be of bronze frame construction having a ½” 
NPT thread.  Water seal assembly shall consist of a Teflon-coat-
ed Belleville spring washer with  top-loaded extruded or cold 
head cup with 3 mm glass bulb containing no plastic parts, and 
having a temperature rating of [155°F (68°C)] [175°F (79°C)].  
Sprinklers shall have a nominal K-factor of 4.4 (62.8).  Standard 
finish: [Bronze] [Chrome-plated] [White Polyester] [Special fin-
ish– specify]. Residential horizontal sidewall sprinklers shall be 
Reliable Model F1 Res 44, SIN R3531 (Bulletin 135).

8.

Summary of Contents for Pantman F1

Page 1: ...rofile decorative de sign The F1 Res Horizontal Sidewall sprinklers Figs 5 6 7 are equally attractive when above ceiling piping can not be used 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 1...

Page 2: ...h for installing Models F1 Res Recessed Pendent CCP SWC sprinklers use only the Model GFR2 sprinkler wrench for installing Model F1 Res Recessed HSW sprin klers use only the Model GFR2 Sprinkler Wrenc...

Page 3: ...5 5 x 5 5 17 64 3 12 0 0 83 20 x 20 6 1 x 6 1 20 75 7 16 7 1 14 Deflector to ceiling Maximum 4 100mm to 8 203mm Max Sprinkler Spacing ft m Flow gpm Lpm Pressure psi bar Sprinkler Identification Numbe...

Page 4: ...Inch mm Sprinkler Temp Rating Max Pressure psi bar Max Ambient Temp K Factor Sprinkler Length Inch mm F C F C 3 4 NPT R 17 32 13 5 155 175 68 79 175 12 100 150 38 66 7 6 2 25 57 Max Sprinkler Spacing...

Page 5: ...tion A Inch mm Max Recessed 7 16 11 Min Recessed 15 16 24 Note Sprinklers shown in Fig 3 and Fig 4 are not suitable for installation in ceil ings which have positive pressure in the space above Techni...

Page 6: ...ch mm Sprinkler Temp Rating F C Flow gpm Lpm Pressure psi bar Sprinkler Identification Number SIN 12 x 12 3 6 x 3 6 4 6 101 152 155 68 175 79 12 45 4 7 5 0 52 R3531 14 x 14 4 3 x 4 3 155 68 175 79 14...

Page 7: ...31 14 x 14 4 3 x 4 3 14 53 0 10 2 0 71 16 x 16 4 9 x 4 9 17 64 3 15 0 1 1 16 x 18 4 9 x 5 5 19 71 8 18 7 1 13 16 x 20 4 9 x 6 1 23 87 1 27 4 1 89 12 x 12 3 6 x 3 6 6 12 152 305 14 52 9 10 2 0 71 14 x...

Page 8: ...ndard finish Bronze Chrome plated White Polyester Special finish specify Recessed escutcheon assembly shall be a steel two piece escutcheon with adjustment Model F2 with adjustment Model F1 of push on...

Page 9: ...er Spe cial finish specify Recessed escutcheon assembly shall be a steel two piece escutcheon with adjust ment Model F2 with adjustment Model F1 of push on and thread off design with adjustment Mod el...

Page 10: ...hroughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dr...

Reviews: