Application
Model F1 Res Sprinklers are used for Residential Fire Pro-
tection according to UL 1626 Standard*. Be sure that ori-
fice size, temperature rating, deflector style and sprinkler
type are in accordance with the latest published standards
of The National Fire Protection Association or the approving
authority having jurisdiction.
Installation
Models F1 Res sprinklers are to be installed as shown.
Model F1, F2 and FP Escutcheons, illustrated herewith,
are the only recessed escutcheons to be used with Model
F1 Res sprinklers. Use of any other recessed escutcheon
will void all approvals and warranties. For installing Model
F1 Res Pendent sprinklers use only the Model D sprinkler
Wrench; for installing Models F1 Res Recessed Pendent,
CCP & SWC sprinklers use only the Model GFR2 sprinkler
wrench; for installing Model F1 Res Recessed HSW sprin-
klers use only the Model GFR2 Sprinkler Wrench. Use of
wrenches other than those specified may damage these
sprinklers. Install F1 Res 44 with a ceiling to deflector dis-
tance of 4” - 12”. Flow arrow on deflector must point away
from near wall and “Top” marking must face ceiling.
Escutcheon*, F1 or F2, Data:
Type
Adjustment
Inch (mm)
“A”
Inch (mm)
Face of
fi
tting
to ceiling
Inch (mm)
F1
3/4 (19.0)
Min.=
3
/
4
” (19.1)
Max.=1
1
/
2
” (38.1)
3
/
16
-
15
/
16
(4.7 - 24.0)
F2
1/2 (12.7)
Min.=
15
/
16
” (23.8)
Max.=1
1
/
2
” (38.1)
3
/
16
-
11
/
16
(4.7 - 17.4)
* Note:
Escutcheons F1 or F2 may be used with
Model F1 Res 49, 58 & 76 Recessed Pendent Sprinkler
Model F1 Res 30, 49, 58 & 76 Pendent
•
Model F1 Res 30 Recessed Pendent / F2
Model F1 Res 49, 58 & 76 Recessed Pendent / F1
•
•
Fig. 1
Fig. 2
F1 escutcheon,
3
/
4
” (19mm) adjustment