background image

5.

Technical Data: F1Res 30 CCP Pendent and Recessed Pendent/FP

Thread

Size

Nominal

Ori

fi

 ce

Inch (mm)

Sprinkler

Temp. Rating

CCP Assembly

Temp. Rating

Max.

Pressure

psi (bar)

Max.

Ambient Temp.

K

Factor

Sprinkler

Length

Inch (mm)

°F

°C

°F

°C

°F

°C

½” NPT 

(R½)

21

/

64

” (8.2)

155

68

135

57

175 (12)

100

38

3.0

2.25 (57)

Max.

Sprinkler Spacing

ft (m)

Flow

gpm (Lpm)

Pressure

psi (bar)

Sprinkler Identi

fi

 cation 

Number

(SIN)

12 x 12 (3,6 x 3,6)

 8 (30.3)

7.0 (0,48)

R3511

14 x 14 (4,3 x 4,3)

 11 (41.6)

13.4 (0,92)

Technical Data: F1Res 49 CCP Pendent and Recessed Pendent/FP

Thread

Size

Nominal

Ori

fi

 ce

Inch

(mm)

Sprinkler

Temp.

Rating

CCP

Assembly

Temp.

Rating

Max.

Pressure

psi (bar)

Max.

Ambient 

Temp.

K

Factor

Sprinkler

Length

Inch 

(mm)

°F

°C

°F

°C

°F

°C

½” NPT 

(R½)

7

/

16

” (11)

155

68

135

57

175 (12) 100 38

4.9

2.25 (57)

Max.

Sprinkler Spacing

ft (m)

Flow

gpm (Lpm)

Pressure

psi (bar)

Sprinkler

Identi

fi

 cation

Number (SIN)

12 x 12 (3,6 x 3,6)

 13 (49)

7.0 (0,48)

R3516

14 x 14 (4,3 x 4,3)

 13 (49)

7.0 (0,48)

16 x 16 (4,9 x 4,9)

14 (53)

8.2 (0,56)

18 x 18 (5,5 x 5,5)

 18 (68.1)

13.5 (0,93)

20 x 20 (6,1 x 6,1)

20 (75.7)

16.7 (1,14)

CCP Options Data:

 “A” 

Cover Adjustment

Inch (mm)

“B”

CCP Height

Inch (mm)

1

/

2

 (12.7)

15

/

16

 (24)

5

/

16

 (7.9)

3

/

4

  (19)

FP Data “A”:

FP Position

“A”

Inch (mm)

Max. Recessed

7

/

16

 (11)

Min.  Recessed

15

/

16

 (24)

Note:

 Sprinklers shown in Fig. 3 and Fig. 4 

are not suitable for installation in ceil-
ings which have positive pressure in 
the space above.

Technical Data: F1Res 58 CCP Pendent and Recessed Pendent/FP

Thread

Size

Nominal

Ori

fi

 ce

Inch (mm)

Sprinkler

Temp. Rating

CCP Assembly

Temp. Rating

Max.

Pressure

psi (bar)

Max.

Ambient Temp.

K

Factor

Sprinkler

Length

Inch (mm)

°F

°C

°F

°C

°F

°C

½” NPT 

(R½)

1

/

2

” (13)

155

68

135

57

175 (12)

100

38

5.8

2.25 (57)

Max.

Sprinkler Spacing

ft (m)

Flow

gpm (Lpm)

Pressure

psi (bar)

Sprinkler Identi

fi

 cation 

Number

(SIN)

12 x 12 (3,6 x 3,6)

 16 (61)

7.6 (0,53)

R3513

14 x 14 (4,3 x 4,3)

 16 (61)

7.6 (0,53)

16 x 16 (4,9 x 4,9)

16 (61)

7.6 (0,53)

18 x 18 (5,5 x 5,5)

 19 (72)

10.8 (0,75)

20 x 20 (6,1 x 6,1)

22 (83.3)

14.4 (1,0)

Technical Data: F1Res 76 CCP Pendent and Recessed Pendent/FP

Thread

Size

Nominal

Ori

fi

 ce

Inch (mm)

Sprinkler

Temp. Rating

CCP Assembly

Temp. Rating

Max.

Pressure

psi (bar)

Max.

Ambient Temp.

K

Factor

Sprinkler

Length

Inch (mm)

°F

°C

°F

°C

°F

°C

3

/

4

” NPT 

(R

3

/

4

)

17

/

32

” (13.5)

155
175

68
79

135

57

175 (12)

100
150

38
66

7.6

2.25 (57)

Max.

Sprinkler Spacing

ft (m)

Flow

gpm (Lpm)

Pressure

psi (bar)

Sprinkler Identi

fi

 cation 

Number

(SIN)

12 x 12 (3,6 x 3,6)

  21 (79.5)

7.6 (0,53)

R7618

14 x 14 (4,3 x 4,3)

  21 (79.5)

7.6 (0,53)

16 x 16 (4,9 x 4,9)

  21 (79.5)

7.6 (0,53)

18 x 18 (5,5 x 5,5)

22 (83.3)

8.4 (0,58)

20 x 20 (6,1 x 6,1)

25 (94.6)

10.8 (0,74)

Summary of Contents for Pantman F1

Page 1: ...rofile decorative de sign The F1 Res Horizontal Sidewall sprinklers Figs 5 6 7 are equally attractive when above ceiling piping can not be used 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 1...

Page 2: ...h for installing Models F1 Res Recessed Pendent CCP SWC sprinklers use only the Model GFR2 sprinkler wrench for installing Model F1 Res Recessed HSW sprin klers use only the Model GFR2 Sprinkler Wrenc...

Page 3: ...5 5 x 5 5 17 64 3 12 0 0 83 20 x 20 6 1 x 6 1 20 75 7 16 7 1 14 Deflector to ceiling Maximum 4 100mm to 8 203mm Max Sprinkler Spacing ft m Flow gpm Lpm Pressure psi bar Sprinkler Identification Numbe...

Page 4: ...Inch mm Sprinkler Temp Rating Max Pressure psi bar Max Ambient Temp K Factor Sprinkler Length Inch mm F C F C 3 4 NPT R 17 32 13 5 155 175 68 79 175 12 100 150 38 66 7 6 2 25 57 Max Sprinkler Spacing...

Page 5: ...tion A Inch mm Max Recessed 7 16 11 Min Recessed 15 16 24 Note Sprinklers shown in Fig 3 and Fig 4 are not suitable for installation in ceil ings which have positive pressure in the space above Techni...

Page 6: ...ch mm Sprinkler Temp Rating F C Flow gpm Lpm Pressure psi bar Sprinkler Identification Number SIN 12 x 12 3 6 x 3 6 4 6 101 152 155 68 175 79 12 45 4 7 5 0 52 R3531 14 x 14 4 3 x 4 3 155 68 175 79 14...

Page 7: ...31 14 x 14 4 3 x 4 3 14 53 0 10 2 0 71 16 x 16 4 9 x 4 9 17 64 3 15 0 1 1 16 x 18 4 9 x 5 5 19 71 8 18 7 1 13 16 x 20 4 9 x 6 1 23 87 1 27 4 1 89 12 x 12 3 6 x 3 6 6 12 152 305 14 52 9 10 2 0 71 14 x...

Page 8: ...ndard finish Bronze Chrome plated White Polyester Special finish specify Recessed escutcheon assembly shall be a steel two piece escutcheon with adjustment Model F2 with adjustment Model F1 of push on...

Page 9: ...er Spe cial finish specify Recessed escutcheon assembly shall be a steel two piece escutcheon with adjust ment Model F2 with adjustment Model F1 of push on and thread off design with adjustment Mod el...

Page 10: ...hroughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dr...

Reviews: