Potter Program #7
Single Interlock Programming Instructions (Single
Hazard - Cross-Zoned, 2 Alarm Zones, 1 Water
fl
ow
Zone and 2 Supervisory Zones)
1. Apply power to panel.
2. Slide the program switch down.
3. Press the FUNCTION button until the display reads “PASS-
WORD = 000.”
4. To enter a password, press the SELECT button until the
proper number is displayed above the “^” symbol; then
press the SET button to move to the next digit. After enter-
ing the third number the display will change. (All panels are
shipped with a “000” password).
5. Press the FUNCTION button until the display reads “PRO-
GRAM ##.” (the second “#” character refers to the current
program number between “0” and “24”).
6. Press the SELECT button until the display reads “PRO-
GRAM #7.”
7. Press the SET button.
8. The panel is completely programmed except for the cus-
tom banner and zone messages. Slide the program switch
back up.
INPUTS:
2 conventional zones (cross-zoned), 1 waterflow zone, 1 low air zone, 1 supervisory zone.
OUTPUTS:
1 general alarm bell, 1 waterflow bell, 1 supervisory bell, 1 solenoid release circuit.
OPERATION: Activation of both conventional zones at the same time will operate the solenoid release circuit and
thegeneral alarm bell.Activation of either conventional zone will operate the general alarm bell.Acti-
vation of the waterflow zone will operate the waterflow bell.Activation of either the low air zone or the
supervisory zone will operate the supervisory bell.When either Zone #1 or #2 is in alarm, Output #1
(general alarm) will operate.When Zones #1 and #2 are in alarm at the same time, Output #4 (solenoid
release) and Output #1(general alarm) will operate.When Zone #3 is in alarm, Output #2 (waterflow
bell) will operate.When either Zone #4 or the supervisory zone is activated, Output #3 (supervisory
bell) will operate.
* The Butter
fl
y valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC
Releasing/Control panel.
Refer to the “Installation, Operation and Instruction Manual” for the PFC-4410-RC Releasing
Control Panel for Additional Information.
POTTER PROGRAM #7
OUTPUTS
ZONES
*Supervisory 2
#1
Conventional
#2
Conventional
#3
Water
fl
ow
#4
Low Air Supervisory
#1 ALARM
X
X
#2 WATERFLOW
X
#3 SUPERVISORY
X
X
#4 RELEASE
X
X
19.
Summary of Contents for DDX PrePaK D
Page 3: ...Fig 1 3...
Page 9: ...9 Fig 3...
Page 10: ...10 Fig 4...
Page 11: ...Fig 5 11...
Page 12: ...Fig 6 12...
Page 13: ...13 Fig 7...
Page 14: ...Fig 8 Wiring Diagram 14...
Page 15: ...15 Fig 9...
Page 16: ...Fig 10 16...
Page 18: ...18 Fig 11 Wiring Diagram...
Page 20: ...20 Fig 12...
Page 22: ...22 Fig 13...
Page 24: ...24 Fig 14...
Page 26: ...26 Fig 15...