background image

2.

General Description

The Reliable Model DDX 4” (100 mm), 6” (150mm) & 8” 

(200mm) PrePaKs are completely self-contained, supervised 
preaction systems that can be readily installed within a floor 
space of 5.15ft

2

 (0.44 m

2

) for the 4” and 6” and 7.5ft

2

 (0.70m

2

)

 

for the 8” (not including door swing).  Installation of the PrePaK 
(not including exterior devices, i.e., detectors and alarm bells), 
requires just three piping connections. These connections are 
the water supply, the sprinkler system, and the drain.  Reference 
locations of these piping connections are shown in Fig.1.  Also, 
two 120 / 220 VAC electrical supply connections are required.  

Note:

 The Model DDX PrePak is available with an optional air 

compressor and an optional Potter Model PFC-4410-RC Re-
leasing/Control Panel wired for a 120 VAC / 60Hz or 220 VAC / 
50 Hz power supply.   

 

Figures 16, 17, and 18 in this Bulletin identify the standard and 

optional equipment available in Reliable Model DDX PrePak, 
Type D, Preaction Systems.

The Reliable Model DDX PrePaK utilizes an optional Potter 

Model PFC-4410-RC Releasing Control Panel. This fully pro-
grammable, microprocessor-based releasing panel is Under-
writers Laboratories, Inc. Listed and is in compliance with NFPA 
13 and NFPA 72.  Because the PFC-4410-RC is totally zone and 
output programmable, the Reliable Model DDX PrePaK can be 
utilized in many different preaction applications without having 
to rewire any of the factory installed devices. Once the previ-
ously described connections are completed, the 24 VDC detec-
tors, output devices, and relay contacts may be connected to 
achieve the desired system implementation.

The Model DDX PrePaK can be used in both single and dou-

ble interlock applications. Reliable Single and Double Interlock 
Preaction Systems are designed for water sensitive areas that 
require protection from inadvertent water flow into the sprinkler 
system piping.

The major benefits of a single/double interlock preaction Sys-

tem, when compared with a wet pipe system, are as follows:
A.  A fire alarm sounds prior to the flow of water from a sprin-

kler, which may enable extinguishing the fire by handheld 
means before the operation of any sprinkler occurs.

B.  An annunciator signals whenever the integrity of piping or 

sprinklers is accidentally or intentionally disturbed; howev-
er, no water flow occurs at that time. 

C.  Detection and notification of a fire condition are provided 

by fire detectors, without the delay associated with water 
delivery time in the event of a fire. Note that with a wet pipe 
system, the fire alarm is delayed until after water has begun 
flowing from an operated sprinkler.

In single interlock applications, one fire detector senses the 

presence of fire, thereby causing the electrical releasing control 
panel to activate notification appliances and energize the sole-
noid releasing valve in the open position. The use of cross-zoned 
detectors will require operation of two detectors before the so-
lenoid valve can open (

Note:

 Verify that the detection method, 

including the use of cross-zoned detection, are permitted by all 
applicable codes and standards, as well as the requirements 
of all authorities having jurisdiction. Cross-zoned detection may 
not be permitted in New York City or by Factory Mutual.) The 

solenoid valve, when closed, preserves supply water pressure 
in the Model DDX valve’s push-rod chamber. Actuating the sole-
noid valve releases that water pressure which allows the Model 
DDX valve to open.

To discharge water from sprinklers on a single interlock system 

with cross-zoned detection, two separate electrical detection 
systems must activate and a sprinkler must open. During the 
early stages of a fire, smoke or heat activates the first detector, 
which causes the control panel to produce a local alarm and an 
alarm at the fire alarm panel. Electrical relays inside the releasing 
control panel can be used to shut down air moving equipment 
or activate security doors and other electrical devices when the 
panel goes into this first condition. Subsequent activation of a 
second, nearby or adjacent detector, on a separate detection 
system, will cause the panel to energize the solenoid valve open 
and release water into the sprinkler piping. Water flowing into 
the sprinkler piping will simultaneously produce water pressure 
that cause the transfer of contacts in the alarm pressure switch 
mounted in the riser assembly, thereby activating a water flow 
alarm device. The flow of water into the sprinkler piping effec-
tively converts the dry system into a wet-pipe sprinkler system. 
In the event that the fire subsequently produces sufficient heat to 
operate a sprinkler, water will flow from that sprinkler.

To flow water into a double interlock preaction system, two 

events must take place: a fire detection device must operate, 
and a pressure switch must be operated by the loss of system 
pressure (sprinkler operation). These two signals, both an elec-
tric signal from the detection system and an electrical signal 
from the pressure (pneumatic) sensor, must coexist at the re-
leasing control panel, which only then will energize the solenoid 
releasing valve, causing water flow into the sprinkler system and 
out of the open sprinkler(s).

In the event that the system piping is ruptured or a sprinkler 

is accidentally opened, the system pressure switch will oper-
ate and an alarm will sound. The Model DDX, Type D Valve as-
sembly, however, will not release water since the solenoid valve 
remains closed due to only one input into the releasing control 
panel.

When using the Reliable Model DDX PrePaK, in either single 

or double interlock applications, the sprinkler system is pressur-
ized (supervised) with air provided by the air compressor and 
is monitored by a system pressure switch. Alternatively, super-
visory system pressure may be provided by a nitrogen source.

A Model B Hydraulic Manual Emergency Releasing station is 

standard equipment in the Model DDX PrePaK. It consists of an 
aluminum nameplate mechanically attached to a ball valve. The 
valve handle in its OFF position is guarded against accidental 
turning to the ON position (and system discharge) by a nylon 
cable tie provided with the PrePaK assembly. The cable tie is 
designed to allow, in case of an emergency, forceful turning of 
the valve handle to the ON position.

Summary of Contents for DDX PrePaK D

Page 1: ...ouble Interlock Electric Electric Release Contents Page General Description 2 Listings and Approvals 4 Technical Data 4 Installation Requirements 5 System Operation 5 6 System Reset Procedure 6 Inspec...

Page 2: ...tection are permitted by all applicable codes and standards as well as the requirements of all authorities having jurisdiction Cross zoned detection may not be permitted in New York City or by Factory...

Page 3: ...Fig 1 3...

Page 4: ...1350lbs 531kg 4 Dimensions System Size Cabinet Dimensions 4 100 mm 6 150 mm 25 7 W x 28 9 D x 68 H 0 65 m W x 0 73 m D x 1 73 m H 8 200mm 30 W x 36 D x 74 H 0 76m W x 0 91m D x 1 88m H 5 Grooved End...

Page 5: ...that contains the 120 220 VAC connections The Reliable Model DDX PrePaK is delivered with five factory installed electrical devices They consist of the following 1 A system air pressure switch which i...

Page 6: ...e controlling water supply to the deluge valve and close the air shutoff valve valve J 2 Close the pushrod chamber supply valve valve A 3 Open the main drain valve valve B and drain system 4 Open all...

Page 7: ...e leasing control panel by operating two detectors For dou ble interlock applications close valve J and open valve H Doing so will discharge the sprinkler system s air pressure 4 Step 3 should result...

Page 8: ...R TBL SYSTEM TBL SUP TBL GROUND FAULT SUP 1 ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY DISCHARGED FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN BUZZER SILENCE SIGNAL SI...

Page 9: ...9 Fig 3...

Page 10: ...10 Fig 4...

Page 11: ...Fig 5 11...

Page 12: ...Fig 6 12...

Page 13: ...13 Fig 7...

Page 14: ...Fig 8 Wiring Diagram 14...

Page 15: ...15 Fig 9...

Page 16: ...Fig 10 16...

Page 17: ...programmed except for the cus tom banner and zone messages Slide the program switch back up 17 INPUTS 1 conventional zone 1 manual release zone 1 waterflow zone 1 low air zone 1 supervisory zone OUTPU...

Page 18: ...18 Fig 11 Wiring Diagram...

Page 19: ...visory bell 1 solenoid release circuit OPERATION Activation of both conventional zones at the same time will operate the solenoid release circuit and thegeneral alarm bell Activation of either convent...

Page 20: ...20 Fig 12...

Page 21: ...tion zone and the low air alarm zone at the same time will operate the solenoid release circuit and the general alarm bell Activation of the conventional zone only will operate the general alarm outpu...

Page 22: ...22 Fig 13...

Page 23: ...ase circuit OPERATION Activation of both conventional zones and the low air alarm zone at the same time will operate the solenoid release circuit and the general alarm bell Activation of either conven...

Page 24: ...24 Fig 14...

Page 25: ...the FUNCTION button until the display reads ZONE 3 OUTPUTS 18 Press the SELECT button The 1 should appear under the v 19 Press the SET button twice The panel is completely pro gramed except for the c...

Page 26: ...26 Fig 15...

Page 27: ...3 1 1 2 Hp 120 VAC 60 Hz Air Compressor Not Available in the 4 100 mm Assembly 0 1 0 No Releasing Control Panel 1 Potter PFC 4410 RC Releasing Control Panel Air Compressor Voltage Unit Size Releasing...

Page 28: ...U S A 10 16 P N 9999970306 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association Factory Mutual Rese...

Reviews: