Potter Program #9
Double Interlock Programming Instructions
(Single Hazard, Cross Zoned, 2 Alarm Zones
(1 Detection & 1 Low Air), 1 Water
fl
ow Zone,
and 1 Supervisory Zone)
1. Apply power to the panel.
2. Slide program switch down.
3. Press the FUNCTION button until display reads “PASS-
WORD=000.”
4. To enter a password, press the SELECT button until the
proper number is displayed above the “^” symbol; then
press the SET button to move to the next digit. After enter-
ing the third number, the display will change. (All panels are
shipped with a “000” password).
5. Press the FUNCTION button until the display reads “PRO-
GRAM ##.” (the second “#” character refers to the current
program number between “0” and “24”).
6. Press the SELECT button until the display reads “PRO-
GRAM #9.”
7. Press the SET button.
8. The panel is completely programmed except for the cus-
tom banner and zone messages. Slide the program switch
back up.
INPUTS: 1 supervisory zone, 1 conventional detection zone, 1 low air supervisory zone, 1 waterflow zone, 1 low
air alarm zone.
OUTPUTS:
1 general alarm, 1 supervisory, 1 waterflow, 1 solenoid release circuit.
OPERATION: Activation of the conventional detection zone and the low air alarm zone at the same time will operate
the solenoid release circuit and the general alarm bell.
Activation of the conventional zone only will operate the general alarm output.
Activation of the low air supervisory zone will operate the supervisory bell output.
Activation of the waterflow zone will operate the waterflow bell output.
Activation of the low air alarm zone will operate the supervisory bell output. It will not operate the alarm
relay.
When Zone #1 is in alarm, Output #1 will operate.
When Zone #2 is activated, Output #3 will operate.
When Zone #3 is in alarm, Output #2 will operate.
When Zone #4 is activated, Output #3 will operate. This will create a supervisory condition not an
alarm condition. The alarm relay will not operate, the supervisory relay will.
When both Zones #1 and #4 are activated at the same time, the solenoid circuit will operate.
* The Butter
fl
y valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC
Releasing/Control panel.
Refer to the “Installation, Operation and Instruction Manual” for the PFC-4410-RC Releasing
Control Panel for Additional Information.
POTTER PROGRAM #9
OUTPUTS
ZONES
*Supervisory 2
#1
Conventional
#2
Low Air
Supervisory
(Empty)
#3
Water
fl
ow
#4
Low Air Alarm
#1 ALARM
X
#2 WATERFLOW
X
#3 SUPERVISORY
X
X
X
#4 RELEASE
X
X
21.
Summary of Contents for DDX PrePaK D
Page 3: ...Fig 1 3...
Page 9: ...9 Fig 3...
Page 10: ...10 Fig 4...
Page 11: ...Fig 5 11...
Page 12: ...Fig 6 12...
Page 13: ...13 Fig 7...
Page 14: ...Fig 8 Wiring Diagram 14...
Page 15: ...15 Fig 9...
Page 16: ...Fig 10 16...
Page 18: ...18 Fig 11 Wiring Diagram...
Page 20: ...20 Fig 12...
Page 22: ...22 Fig 13...
Page 24: ...24 Fig 14...
Page 26: ...26 Fig 15...