background image

6.

After system shutdown and draining, the Model DDX Deluge 

Valve is easily reset without special tools (see Fig. 9 or 10). Re-
store detection devices by resetting or replacing any operated 
device. Once detection devices are restored, (the Potter Model 
PFC-4410-RC Releasing Control Panel reset), and supply pres-
sure is re-supplied to the push-rod chamber, the deluge valve 
is reset.

System Operation (Double Interlock)

To fully activate (water flow) the Reliable Model DDX 4” (100 

mm), 6” (150 mm) or 8” (200 mm) PrePaK in a double interlock 
application, two independent events must coexist. An electrical 
fire detection device (smoke, heat, etc.) and the system air pres-
sure switch must be activated.  This pressure switch is activated 
by a reduction of the system’s pneumatic pressure (as a result of 
sprinkler operation).  Both of these events will cause the control 
panel to energize the solenoid valve, thereby releasing water 
through the deluge valve and into the sprinkler system.  The ini-
tiation of either one of these events will only cause an alarm to 
annunciate, and will not fill the sprinkler system.

When the double interlock preaction system is set for service, 

the supply pressure acts both on the underside of the deluge 
valve’s clapper and on the valve’s push rod by means of the 
pressurized push rod chamber. The pressure force acting on 
the push rod, when utilized with the mechanical advantage of 
the deluge valve’s lever, is more than sufficient to hold the clap-
per in the closed position against the water supply pressure. 

Energizing the releasing solenoid valve allows the deluge 

valve’s push-rod chamber to be vented to drain through its 
outlet. Since the pressure cannot be replenished through the 
inlet restriction as rapidly as it is vented though the outlet, the 
push-rod chamber pressure falls rapidly. When the push-rod 
chamber pressure drops below one-third of the supply pres-
sure, the opening force acting beneath the clapper becomes 
greater than the push-rod force acting on the lever.  This causes 
the clapper to open. Refer to Reliable Bulletins 518 and 519 for 
further details.

Once the clapper has opened, the lever acts as a latch, pre-

venting the clapper from returning to the closed position. Water 
from the supply flows through the deluge valve into the system 
piping. Water also flows through the deluge valve alarm outlet 
to activate any water flow alarm devices. Note that the solenoid 
valve will be maintained open by the Potter Model PFC-4410-
RC Releasing Control Panel’s latching feature until it is reset for 
operation.

After system shutdown and draining, the Model DDX Deluge 

Valve is easily reset without special tools (see Fig. 9 or 10). Re-
store detection devices by resetting or replacing any operated 
device. Once detection devices are restored, (the Potter Model 
PFC-4410-RC Releasing Control Panel reset), and supply pres-
sure is re-supplied to the push-rod chamber, the deluge valve 
is reset.

Resetting Single And Double Interlock Systems

Refer to Fig. 9 or 10.
1.  Close the main valve controlling water supply to the deluge 

valve and close the ¼” air shutoff valve, valve J.

2.  Close the pushrod chamber supply valve, valve A.
3.  Open the main drain valve, valve B, and drain system.
4.  Open all drain valves and vents at low points throughout 

the system, closing them when flow of water has stopped.  
Open valve D.  

Note:

  The above steps accomplish the 

relieving of pressure in the pushrod chamber of the deluge 
valve.

5.  Push in the plunger of ball drip valve, valve F, to force the 

ball from its seat, and drain any water in the alarm line. 

6.  With the Model B Manual Emergency Station, valve D, 

open, push in and rotate the deluge valve’s external reset 
knob clockwise until you hear a distinct clicking noise, indi-
cating that the clapper has closed.  

Note:

 The reset knob 

can be rotated only after pressure in the pushrod chamber 
is reduced to atmospheric conditions (0 psig).

7.  Inspect and replace any portion of the sprinkler system 

subjected to fire conditions.

8.  Verify that the following valves are in their respective posi-

tions:
 valve C – open, valve E – closed, valve H – closed,
 valve K – open, valve M – closed. 

9.  Open valve A and allow water to fill the deluge valve’s push-

rod chamber.  Close valve D.

10.  Bleed any air from the actuation piping by energizing the 

solenoid valve.  This is done by operating a detector or an 
electric manual emergency station.  While water is flowing 
through the solenoid valve, cause it to close by pressing the 
system reset button on the Potter PFC-4410-RC Releasing 
Control Panel.  

Note:

  All detection devices must be reset 

before the releasing/control panel can be reset.

11.  Open the ¼” air shutoff valve, valve J, to restore air pres-

sure in the sprinkler system.  The rapid air-fill shutoff valve, 
valve M, may be opened here to expedite the filling of the 
sprinkler system.

12.  Open slightly the main valve controlling water supply to the 

Model DDX Deluge Valve, closing drain valve B when wa-
ter flows.  Observe if water leaks through the ball drip valve, 
valve F, into the drip cup or drain manifold, G.  If no leak 
occurs, the deluge valve’s clapper is sealed.  Open slowly, 
and verify that the main valve controlling water supply is 
fully opened and properly monitored.

13.  Verify that valve A is open.
14.  Secure the handle of the Model B Manual Emergency Sta-

tion, valve D, in the OFF position with a nylon tie (supplied 
with the assembly).

15.  Press the system reset button on the Potter PFC-4410-RC 

Panel to place the system in the ready condition.  

Note:

  All 

detection devices must be reset before the panel can be 
reset.

Maintenance

The Reliable Model DDX PrePaK and associated equipment 

shall periodically be given a thorough inspection and test. NFPA 
25, Standard for the Inspection, Testing and Maintenance of 
Water Based Fire Protection Systems, provides minimum main-
tenance requirements. Systems should be tested, operated, 
cleaned and inspected at least annually, and parts replaced as 
required. Periodically open the air/condensate drain valve (refer 
to Fig. 9 or 10) beneath the air tank to drain any condensate ac-
cumulation. Bulletin 518 provides information for maintaining the 
Model DDX Deluge Valve. Potter Manual #5403550 provides 
information for maintaining the PFC-4410-RC Releasing Control 
Panel.

Summary of Contents for DDX PrePaK D

Page 1: ...ouble Interlock Electric Electric Release Contents Page General Description 2 Listings and Approvals 4 Technical Data 4 Installation Requirements 5 System Operation 5 6 System Reset Procedure 6 Inspec...

Page 2: ...tection are permitted by all applicable codes and standards as well as the requirements of all authorities having jurisdiction Cross zoned detection may not be permitted in New York City or by Factory...

Page 3: ...Fig 1 3...

Page 4: ...1350lbs 531kg 4 Dimensions System Size Cabinet Dimensions 4 100 mm 6 150 mm 25 7 W x 28 9 D x 68 H 0 65 m W x 0 73 m D x 1 73 m H 8 200mm 30 W x 36 D x 74 H 0 76m W x 0 91m D x 1 88m H 5 Grooved End...

Page 5: ...that contains the 120 220 VAC connections The Reliable Model DDX PrePaK is delivered with five factory installed electrical devices They consist of the following 1 A system air pressure switch which i...

Page 6: ...e controlling water supply to the deluge valve and close the air shutoff valve valve J 2 Close the pushrod chamber supply valve valve A 3 Open the main drain valve valve B and drain system 4 Open all...

Page 7: ...e leasing control panel by operating two detectors For dou ble interlock applications close valve J and open valve H Doing so will discharge the sprinkler system s air pressure 4 Step 3 should result...

Page 8: ...R TBL SYSTEM TBL SUP TBL GROUND FAULT SUP 1 ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY DISCHARGED FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN BUZZER SILENCE SIGNAL SI...

Page 9: ...9 Fig 3...

Page 10: ...10 Fig 4...

Page 11: ...Fig 5 11...

Page 12: ...Fig 6 12...

Page 13: ...13 Fig 7...

Page 14: ...Fig 8 Wiring Diagram 14...

Page 15: ...15 Fig 9...

Page 16: ...Fig 10 16...

Page 17: ...programmed except for the cus tom banner and zone messages Slide the program switch back up 17 INPUTS 1 conventional zone 1 manual release zone 1 waterflow zone 1 low air zone 1 supervisory zone OUTPU...

Page 18: ...18 Fig 11 Wiring Diagram...

Page 19: ...visory bell 1 solenoid release circuit OPERATION Activation of both conventional zones at the same time will operate the solenoid release circuit and thegeneral alarm bell Activation of either convent...

Page 20: ...20 Fig 12...

Page 21: ...tion zone and the low air alarm zone at the same time will operate the solenoid release circuit and the general alarm bell Activation of the conventional zone only will operate the general alarm outpu...

Page 22: ...22 Fig 13...

Page 23: ...ase circuit OPERATION Activation of both conventional zones and the low air alarm zone at the same time will operate the solenoid release circuit and the general alarm bell Activation of either conven...

Page 24: ...24 Fig 14...

Page 25: ...the FUNCTION button until the display reads ZONE 3 OUTPUTS 18 Press the SELECT button The 1 should appear under the v 19 Press the SET button twice The panel is completely pro gramed except for the c...

Page 26: ...26 Fig 15...

Page 27: ...3 1 1 2 Hp 120 VAC 60 Hz Air Compressor Not Available in the 4 100 mm Assembly 0 1 0 No Releasing Control Panel 1 Potter PFC 4410 RC Releasing Control Panel Air Compressor Voltage Unit Size Releasing...

Page 28: ...U S A 10 16 P N 9999970306 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association Factory Mutual Rese...

Reviews: