Custom Program #1
(For New York City Compliance)
Single Interlock Programming Instructions for
New York City Compliance (Single Hazard, 2 Alarm
Zones, 1 Water
fl
ow Zone, and 2 Supervisory Zones)
1. Apply power to the panel.
2. Slide the program switch down.
3. Press the FUNCTION button until the display reads “PASS-
WORD=000.”
4. To enter a password, press the SELECT button until the
proper number is displayed above the “^” symbol; then
press the SET button to move to the next digit. After enter-
ing the third number, the display will change (All panels are
shipped with a “000” password).
5. Press the FUNCTION button until the display reads “PRO-
GRAM ##” (the second “#” character refers to the current
program number between “0” and “24”).
6. Press the SELECT button until the display reads “PRO-
GRAM #6.”
7. Press the SET button.
8. Slide the program switch up.
9. Slide the program switch down.
10. Apply steps 3 to 5.
11. Press the SELECT button until the display reads “PRO-
GRAM #0.”
12. Press the SET button.
13. Press the FUNCTION button until the display reads “OUT-
PUT 1: INDICATING.”
14. Press the SET button until the display reads “OUTPUT #2:
INDICATING.”
15. Press the SELECT button until the display reads “TROUBLE
BELL.” Press the SET button.
16. Press the FUNCTION button until the display reads “ZONE
1 OUTPUTS.” The “v” is pointing to the first available out-
put for the zone indicated on the display. If the number is
displayed, it is turned on for that zone. If the number is not
displayed, the zone is turned off.
17. Press the FUNCTION button until the display reads “ZONE
3 OUTPUTS.”
18. Press the SELECT button. The “1” should appear under the
“v”.
19. Press the SET button twice. The panel is completely pro-
gramed except for the custom banner and zone mes-
sages. If these messages are not desired, then slide the
program switch back up.
INPUTS:
1 conventional zones, 1 manual release zone, 1 waterflow zone, 1 low air zone, 1 supervisory zone.
OUTPUTS:
1 general alarm bell, 1 trouble bell, 1 supervisory bell, and 1 solenoid release circuit.
OPERATION: Activation of either the conventional zone or the manual release will operate the solenoid release
circuit and the general alarm bell.
Activation of the waterflow zone will operate the general alarm bell.
Activation of either the low air zone or the supervisory zone will operate the supervisory bell.
A trouble condition (low battery, wiring problem, etc.) will operate the trouble bell.
When either Zone #1 or #2 is in alarm, Output #1 (general alarm) and Output #4 (solenoid release)
will
operate.
When Zone #3 is in alarm, Output #1 (alarm bell) will operate.
When either Zone #4 or the supervisory zone is activated, Output #3 (supervisory bell) will operate.
When the panel is in a trouble condition, Output # 2 (trouble bell) will operate.
* The Butter
fl
y valve in the PrePaK assembly is connected to Supervisory 2 input of the Potter PFC-4410RC
Releasing/Control panel.
Refer to the “Installation, Operation and Instruction Manual” for the PFC-4410-RC Releasing
Control Panel for Additional Information.
POTTER PROGRAM #1
OUTPUTS
ZONES
*Supervisory 2
#1
Conventional
#2
Manual release
#3
Water
fl
ow
#4
Low Air
Supervisory
#1 ALARM
X
X
X
#2 TROUBLE
#3 SUPERVISORY
X
X
#4 RELEASE
X
X
25.
Summary of Contents for DDX PrePaK D
Page 3: ...Fig 1 3...
Page 9: ...9 Fig 3...
Page 10: ...10 Fig 4...
Page 11: ...Fig 5 11...
Page 12: ...Fig 6 12...
Page 13: ...13 Fig 7...
Page 14: ...Fig 8 Wiring Diagram 14...
Page 15: ...15 Fig 9...
Page 16: ...Fig 10 16...
Page 18: ...18 Fig 11 Wiring Diagram...
Page 20: ...20 Fig 12...
Page 22: ...22 Fig 13...
Page 24: ...24 Fig 14...
Page 26: ...26 Fig 15...