9.1.2 Bus Status, LED2
red LED
Cause
Remedy
OFF
No error
–
0.5 Hz
−
F-Parameterization defective,
e.g. incorrectly set PROFIsafe
destination address
F_Dest_Add
−
Incorrectly configured
F_iPar_CRC
value
−
Check the adjusted PROFIsafe destination
address. Valid PROFIsafe destination
addresses: 1–99, see chapter PROFIsafe
Destination address “F_Dest_Add” on page 24
−
The checksum calculated for the defined
iParameter set is incorrect, or was not included
in the projection, see chapter "Parameter
Definition / CRC Calculation" on page 45
ON
−
No connection to the
IO-Controller
−
Check Device name, IP-address and
Subnet mask
9.1.3 Link Status, PORT1:LED3; PORT2:LED5
green LED
Cause
Remedy
OFF
Voltage supply absent or too low
Check voltage supply and wiring
No Ethernet connection
Check Ethernet cable
Hardware error,
measuring system defective
Replace measuring system
ON
Measuring system ready for
operation, Ethernet connection
established
-