Commissioning
TR-Electronic GmbH 2012, All Rights Reserved
Printed in the Federal Republic of Germany
Page 36 of 56
TR - ECE - BA - GB - 0095 - 19
05/30/2018
5.5.1.1.5 Safe status
Unsigned8
Byte
X+10
Bit
7 – 0
Data
2
7
– 2
0
Bit Description
2
0
iPar_OK:
New iParameter values have been assigned to the F-Device
2
1
Device_Fault:
Error in F-Device or F-Module
2
2
CE_CRC:
Checksum error in communication
2
3
WD_timeout:
Watchdog timeout during communication
2
4
FV_activated:
Fail-safe values activated
2
5
Toggle_d:
Toggle bit
2
6
cons_nr_R:
Virtual consecutive number has been reset
2
7
reserved
Safe status can only be indirectly accessed from the safety program with the aid of
variables, see chapter "Access to the safety-oriented data channel" on page 47.
A detailed description of the status bits can be taken from the PNO document
"PROFIsafe – Profile for Safety Technology on PROFIBUS DP and PROFINET IO“,
Order No.: 3.192b.