6.2.3. - Output Signal
This menu determines the type of pump used: Solar pumps perform at their highest
power when the signal is also at its maximum, heating pump on the other hand are set
to highest power when the control signal is at its minimum.
Solar = Normal, Heating pumps = Inverted.
Setting range: Normal, Inverted / Default setting: Normal
6.2.4. - PWM Off / 0-10V Off
This signal is put out when the pump is switched off (pumps that can detect cable
break need a minimum voltage).
Setting range: Solar: 0 to 50 % / Default setting: 0 %
HP:
50 to 100 %/ Default setting: 100 %
6.2.5. - PWM Zap / 0-10V Zap
This signal is needed to turn the pump on at minimum speed.
Setting range: Solar: 0 to 50 % / Default setting: 10 %
HP: 50 to 100 % / Default setting: 90 %
6.2.6. - PWM Max / 0-10V Max
This determines the output voltage for the maximum performace of the pump that is
used e.g. during purging or manual operation.
Setting range: Solar:
50 to 100 % / Default setting: 100 %
HP:
0 to 50 % / Default setting: 0 %
Displays the set signal in text and a graphical diagram.
6.2.7. - Show signal