23
Settings
4.14.7. - Periods
Set the desired periods of time when the thermostat should be active. 2 periods can
be set per day, settings can also be copied to other days. Outside the set times the
auxiliary heat source is switched off.
Setting range: from 00:00 to 23:59 / Default setting: 06:00 to 22:00
4.15. - Recirculation
Time- and temperature controlled operation of hot water recirculation pump.
4.15.1. - Min. set temperature
If temperature at the hot water sensor drops below this temperature during the period
when HW recirculation is active (see 4.15.7), the recirculation pump is switched on.
Setting range: 10 °C to 90 °C / Default setting: 51°C
4.15.2. - Hysteresis
Hysteresis of the preset temperature.
Setting range: 1 K to +20 K / Default setting: 5 K
4.15.7. - Recirculation time programs
Set the desired periods of time when recirculation should be active. 2 periods can
be set per day, settings can also be copied to other days. Outside the set times
recirculation is switched off.
Setting range: from 00:00 to 23:59 / Default setting: 06:00 to 22:00