21
Sensor S(X) switch-off temperature
If the temperature at sensor S(X) exceeds the value of TmaxS(X) and the other conditi-
ons are also met, then the controller switches off the associated pump and/or valve. If
the temperature at the sensor S(X) drops below this value, then the pump and/or the
valve are switched on again.
Setting range: 0-99 °C / Default setting: 60 °C
Temperature values which are set high will allow higher solar heat accu-
mulation but it shall be checked that all system components are resis-
tant to high temperatures and scalding protection is provided. Regulus
solar thermal systems are safe for heating water up to 95 °C.
Danger
4.4. -
∆
T R2
Settings
4.5. - Tmax S(X)