49
on/off (on/off)
Switching the timer function on/off.
on 1 (hh:mm)
The first period switch-on time.
off 1 (hh:mm)
The first period switch-off time.
on 2 (hh:mm)
The second period switch-on time.
off 2 (hh:mm)
The second period switch-off time.
reset state of T1 T2 with every start of the period of the program
When this function is
On, at every start of time period in time program the state of both
thermostats will be reset according to the current temperature.
S 2.18 – HW Address Setting for CIB Modules
An add-on module can be connected to the Controller on CIB bus. The module is also
power-supplied from this bus. After the module is connected, its HW address shall be set
using either the web interface or the Controller display; otherwise the module will not work
together with the Controller.
Check the module HW address (it is printed on its side) and fill it in the HW module address
line and press Load address. After that, the module should start working with the IR12
Controller.
HM mod. addr.
HW address of the module, entered in hexadecimal format.
load address
A key to confirm the address. If the address is entered right, the lower line will
read OK.