setback
setting heating water temperature reduction calculated from the OTC curve
when the mode changes from comfort to setback as preset by the time
schedule.
The Winter/Summer function is active if the zone is in Auto mode. The Controller will set the
zone temperatures by the parameters set. If the outdoor temperature equals or exceeds the
preset one for the specified number of hours, the zone will switch to Summer mode.
state
shows the current mode. If the Winter/Summer function is turned off, Winter is
shown permanently here.
summer temp
temperature threshold to switch to Summer mode.
summer time
waiting time before switching to Summer mode.
winter temp
temperature threshold to switch to Winter mode.
winter time
waiting time before switching to Winter mode.
2.2 Setting temperatures for hot water storage tank
When there is demand for hot water storage tank to be heated up, the boiler is switched on
to max. output temperature, however no more than 70°C, and the DHW diverter valve is
shifted.
T comfort comfort temperature. Hot water storage tank gets heated up to this temperature if the
program is set to “Comfort” at the moment.