38
state (active/off)
Turning frost protection on/off.
out. temp. (°C)
Setting outdoor temperature limit below which Frost protection is activated.
water temp. (°C) Heating water temperature kept in a zone when Frost protection is active.
Critical temperature in Thermal Store:
If the temperature in Thermal Store exceeds the set critical temperature, cooling will start
with heating into all zones switched on in Service level, i.e. incl. those switched off in User
level. During cooling, the zone pump is on and the max. temperature is set for the zone
(
Max.t to zone
). Cooling will be finished when the Thermal Store temperature sinks by 5°C.
temperat. (°C)
Setting the critical temperature for Thermal Store.
Anti-block function:
When this function is active, selected heating elements (pumps, valves) are spun for a while
once a week (at a preset day and time). If any of these components was in operation the
previous week due to the Controller intervention, this anti-block function will not apply.
state (active/off)
Switching on (off) the function of component spin.
day (Mo - Su)
Selection of day when the spin shall occur.
hour (0 - 23)
Hour when the spin starts.