S 2.11 – Universal outputs 0-10V
uni1, uni2
Assign universal analogue outputs, options are:
off
output is not used
fire damper
damper on the fireplace combustion air inlet is assigned
DHW circ.p.
DHW recirculation pump (switched) is assigned to this output
src. 0-10V
0-10V source signal is assigned to this output
S 2.12 – SMS Setting
ON (ON/OFF)
Turning on (off) the text message functions (text functions will be
available for setting in the User Menu on the web and on the display
as well).
S 2.13 – Heat and Flow Rate Measurement Settings
ON (ON/OFF)
Turning on (off) the heat and flowrate measurement function.
flowmeter (ON/OFF)
Option ON shall be selected when the flowrate is measured by a pulse
flowmeter wired to the logical input terminal, marked C9 on the
Controller.