RVA25-24A

SW2

Free stroke (auto adaptation, 
10...52 mm) (FS)

Fixed stroke (40 mm) 

SW3

Linear

Equal percentage (FS)

SW4

Y = 2...10 V DC

Y = 0...10 V DC (FS)

SW5

Reverse action

Direct action (FS)

SW6

Y signal split

SW7 disable (FS)

SW7

5(6)...10 V = 0...100%

0(2)...5(6) V = 0...100% 
(FS)

Flow characteristics SW3 

Off will give equal percentage flow characteristic with 

GTRS125-215 

and GTRS150-310, as well as GTVS125-215 and GTVS150-310. Off is 
the recommended setting.

On will give linear flow characteristic with 

GTRS125-215 and 

GTRS150-310, as well as GTVS125-215 and GTVS150-310. 
 
Direct action/Reverse action (SW5) 
In direct action, the actuator will drive the spindle down on increasing 
control signal. In reverse action, it will drive the spindle up on increas-
ing control signal. The setting of SW5 will not affect the direction of 
movement for the override function.

Split function (SW6 and SW7)
Two actuators can share the same control signal with a split function. 
Depending on the setting of SW6, the function is enabled or disabled. 
SW7 decides the working range of the actuator.

LEDs

The actuator has two LEDs with indications according to the table 

below.

Indication

Green steady light

Actuator working properly

Green light quick flashing

Test run in progress

Green light slow flashing

The setting was changed during the 
operation. The new setting will be 
valid after the next power on.

Red and green steady light

End position reached

Red light slow flashing

Override operating mode

Red steady light

Operation faulty, either the improper 
installation or the valve stroke lost

 

2

EMC compatibility

This product conforms with the EMC requirements of European harmo-
nised standards EN60730-1:2000 and EN60730-2-8:2002 and carries the 
CE mark.

LVD

This product conforms with the requirements of European LVD  
standards EN60730-1:2000 and EN60730-2-8:2002.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regin.se, [email protected]

e

i

Läs denna instruktion innan produkten 

monteras och ansluts

INSTRUKTION

 

RVA25-24A

Ventilställdon för 0(2)...10 V-styrning

RVA25-24A är ett ventilställdon för styrning av GTRS125-215 och 

GTRS150-310, samt GTVS125-215 och GTVS150-310. Ställdonet har 

automatisk lyfthöjdsjustering och kan köras manuellt.

Tekniska data

Matningsspänning  

24 V AC ±15%, 50/60 Hz 

Styrsignal 

 

0(2)...10 V DC 

Effektförbrukning   

Max. 12 W 

Slaglängd 

 

10...52 mm (40 mm fast slaglängd) 

Ställtid 

 

3 s/mm 

Ställkraft 

 

2 500 N 

Omgivningstemperatur 

0...50ºC 

Lagringstemperatur 

-40...80°C 

Omgivande luftfuktighet 

10...90% RH 

Mått (BxHxD) 

 

200 x 300 x 135 mm 

Skyddsklass 

 

IP54

Montering

Om ventilens spindeladapter och ventilhalsadapter inte redan är 

monterade på ventilen, montera dem. Dra ut ventilspindeln så långt 

det går. 

Ta bort låsklamman (U-klamman) från ställdonets ok. För in ventilspin-

deln i oket och se till att spindeladaptern passar i hålet i det vinklade 

järnet på ställdonets drivspindel.

Spåret i ventilhalsadaptern måste vara i linje med monteringshålen 

för U-klamman på ställdonet. Om spindeln behöver flyttas in eller ut 

för att detta ska ske, tryck ned mittenknappen på manöverratten och 

vrid denna medurs för att flytta ut spindeln, och moturs för att flytta in 

spindeln (se Manuell överstyrning). För in U-klamman när ventilen är i 

rätt läge. Dra åt muttrarna tills ventilen sitter stadigt fast. 

Nedmontering i omvänd ordning.

Monteringspositioner

85º

85º

SV

Summary of Contents for RVA25-24A

Page 1: ...c stroke and endpoint calibration will take place If the unit has been configured for fixed stroke DIP switch 2 in position Off the actuator will first go to the fully closed end position The position will be stored in memory and the stroke will be calculated from this point If the unit has been configured for free stroke DIP switch 2 in posi tion On the actuator will first go to both endpoints of...

Page 2: ...ct conforms with the EMC requirements of European harmo nised standards EN60730 1 2000 and EN60730 2 8 2002 and carries the CE mark LVD This product conforms with the requirements of European LVD standards EN60730 1 2000 and EN60730 2 8 2002 Contact AB Regin Box 116 428 22 Kållered Sweden Tel 46 31 720 02 00 Fax 46 31 720 02 50 www regin se info regin se i Läs denna instruktion innan produkten mon...

Page 3: ...ändringar av inställningen för SW2 kommer att träda i kraft direkt Förändringar av de andra inställningarna kommer att ignoreras under drift Nya inställningar kommer endast att gälla efter nästa spänningstillslag 1 On 0 Off SW1 Spindel upp vid sluten kontakt Spindel ned vid sluten kon takt FI fabriksinställning SW2 Fri slaglängd autoanpass ning 10 52 mm FI Fast slaglängd 40 mm SW3 Linjär Likprocen...

Page 4: ... auf den richtigen Sitz des Montagebügels in der Nut des Ven tiladapters Muss die Spindel nach oben oder nach unten bewegt werden drücken Sie die Handbedientaste und drehen diese im Uhrzeigersinn so dass sich die Stellantriebsspindel nach oben bewegt und gegen den Uhrzeigersinn so dass sie sich nach unten bewegt siehe Hand bedienung Sobald das Ventil sich in der korrekten Position befindet wird di...

Page 5: ...richt den Anforderungen des Europäischen LVD Standards EN60730 1 2000 und EN60730 2 8 2002 Kontakt RICCIUS SOHN GmbH Vertriebsbüro Deutschland Haynauer Str 49 12249 Berlin Tel 49 30 77 99 40 Fax 49 30 77 99 413 info riccius sohn eu www riccius sohn eu Moteur de vanne pour contrôle 0 2 10 V RVA25 24A est un actionneur prévu pour le réglage des van nes GTRS125 215 et GTRS150 310 ainsi que GTVS125 21...

Page 6: ...re manuelle l actionneur lance une calibra tion automatique de la course et des points de fin de course Interrupteurs DIP Il y a sept interrupteurs DIP qui permettent de configurer les différentes fonctions de l actionneur Voir le tableau ci dessous pour plus de détails Les changements de réglage apportés à SW2 sont immédiatement pris en compte Les changements sur les autres positions sont ignorés...

Page 7: ...ENELEC EN60730 1 2000 et EN60730 2 8 2002 et porte la marque CE Directive basse tension 2006 95 EC Ce produit est conforme aux exigences de la directive BT et répond aux normes EN60730 1 2000 et EN60730 2 8 2002 Contact Regin Control SARL 32 rue Delizy 93500 Pantin Tél 01 71 00 34 Fax 01 71 46 46 www regin fr info regin fr 7 ...

Reviews: