24
|
P36E-11 Zero Clearance Direct Vent Gas Fireplace
installation
FINISHING
Non-combustible
Material
J-style Trim
or metal corner bead
may be used to finish these
edges
Combustible
Material
Combustible
Material
Diagram 3
IMPORTANT FINISHING DETAIL NOTE:
Before placing unit into final position - it is important to know the total
thickness / height of finished hearth (tile, carpet, etc.) The base of the
fireplace should be level or higher than the finished hearth height.
Diagram 4 - Shown with optional finishing trim
Note:
All non-combustible and combustible facing material should
butt up cleanly to the flanges around the firebox opening.
Rough edges will be visible from the front view with the Vignette
faceplate - if not using the optional finishing trim.
To maintain a clean finished edge - it is recommended to install
the combustible facing material with the finished edge against the
fireplace / nailing strips.
Alternatively, you can use J Style Trim or Metal Corner Bead
to cover cut edges of the non-combustible facing material.
31-1/2
"
Diagram 2
Note: 40-1/2" (1029mm) is the minimum
height for both flex termination or
rigid pipe venting.
Note: The unit does not have to be
completely enclosed in a chase. The
clearance on top of the unit is 0" to the
standoffs so combustible building
materials can be laid directly on top
of the standoffs. You must maintain
1-1/2" (38mm) clearance from the
vent to combustible materials for
flex (1-1/4" for Rigid Pipe).
Use steel studs for framing where the 1-1/2"
(38mm) clearance from the vent to combustible
material cannot be maintained, e.g. front top
header.
Diagram 1