32
|
P36E-11 Zero Clearance Direct Vent Gas Fireplace
installation
RIGID PIPE VENTING ARRANGEMENTS
HORIZONTAL TERMINATIONS
Regency DIRECT VENT SYSTEM (FLEX)
(Propane & Natural Gas)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
o
elbow (two 45
o
elbows equal one 90
o
elbow).
Note: Must use optional rigid pipe adaptor (Part # 510-994) when using Rigid Pipe venting systems.
All Rigid Pipe Systems
4" inner diameter
6-5/8" outer diameter
Regency Flex Vent
4" inner diameter
6-7/8" inner diameter
• Maintain clearances to combustibles.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each floor level and whenever passing through a wall.
A vent guard should be used
whenever the termination is lower
than the specified minimum or as
per local codes.
Note: Regency Direct Vent
System (Flex Part #'s
946-515, 946-516) is only
approved for horizontal
terminations.