Regency G51 UltraGlow
7
INSTALLATION
GAS CONNECTION
2004.
3)
Locate the center point where the flue will
pass through the chimney above the appli-
ance. Move the appliance into the exact
location where it is to be installed. Ensure
that the Insert is level.
GAS CONNECTION WARNING:
Only persons licensed to work with
gas piping may make the necessary
gas connections to this appliance.
1)
If the appliance is to be installed into an
existing chimney system, thoroughly clean
the masonry or factory built fireplace.
2)
The gas line should be rigid pipe. Copper
may also be used if approved by AS5601-
MINIMUM FIREPLACE
DIMENSIONS
The minimum fireplace dimensions for the Re-
gency gas space heater are shown in the
following diagrams:
NOTE: A non-combustible mantel may be
installed at a lower height if the
framing is made of metal studs
covered with a non-combustible
board.
MINIMUM
CLEARANCES TO
COMBUSTIBLES
The minimum fireplace clearances for the Re-
gency gas space heater are shown in the
following diagrams:
From Unit
Sides
A
305 mm
Ceiling
B
914 mm
Mantel
C
204mm
Floor
H
100mm
Min. Alcove Width
K
1435 mm
Max. Alcove Depth
L
915 mm
Mantle
D
305mm
SPECIFICATIONS
NG
ULPG
INJECTOR #29
#46
SIZE
3.45mm
2.06mm
INPUT
Min. 25 mj/h Min. 23 mj/h
RATING
Max. 50 mj/h Max. 50 mj/h
SUPPLY Min. 1.13k Pa Max. 2.75 kPa
PRESSURE
REGULATOR
TEST POINT
Max. 0.90 kPa Max. 2.61 kPa
PRESSURE