Regency G51 UltraGlow
8
INSTALLATION
TEST FOR FLUE
SPILLAGE
A "spillage" test must be made before
the installed unit is left with the custom-
er. Follow the procedure below:
1)
Start all exhaust fans in the home and then
close all external doors and windows in the
house.
2)
Light the unit and set controls to maximum.
Turn fan off.
3)
After five minutes, test that there is a pull
on the flue by placing a smoke match,
cigarette or similar device which gives off
smoke, in position as shown.
Light a match close to centre. Check
if smoke is drawn inside flue.
Diagram 1
GAS AERATION
SETTING
The burner aeration is factory set but may need
adjusting due to either the local gas supply, air
supply or altitude. This adjustment is per-
formed by the installer.
NG:
5 mm open
ULPG
10 mm open
Note: Any damage due to carboning re-
sulting from improperly setting
the aeration controls is NOT cov-
ered under warranty.
FLUEING
THE APPLIANCE MUST NOT BE CONNECTED
TO A CHIMNEY FLUE SERVING A SEPARATE
SOLID FUEL BURNING APPLIANCE.
This appliance is designed to attach to a 200 mm
diameter type B-Vent or listed gas fuel type vent
liner running the full length of the chimney. A flue
height of 3.6 m. is recommended, the minimum
being 1.53 m.
Periodically check that the flue is unrestricted
and an adequate draft is present when the unit
is in operation.
Before installing flue system ensure that the
damper plate is open and secure to prevent the
damper plate from falling down and crushing
the liner.
Install to AS5601-2004, (Australia) NZS 5261
(New Zealand).
Combustion and Ventilation Air
WARNING: This appliance needs fresh
air for safe operation and must be in-
stalled with provisions for adequate
combustion and ventilation air available
to the room in which it is to be operating.
Air for combustion is drawn in through the front
of the unit, therefore, the front of the unit must
be kept clear of any obstructions.
GAS PRESSURE TEST
The unit is preset to give the correct gas input
rate. The pressure setting at the test point is:
NG
0.90 kPa
ULPG
2.61 kPa
and is measured at the adjustable pressure
regulator with the appliance operating on "high".
The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified.
INSTALLATION OF
FLUE GATHER
1)
Line up flue gather with the holes on the
firebox.
2)
Secure in place with 16 screws.
Outlet Pressure
Test Point: Factory Set
Do Not Measure or Adjust.