52
.............................................
|City Series CV60E-1
installation
52 | City Series CV60E-1
Vent Guard - if required*
(Part #946-
604
/P)
5" (127 mm)
8" (203 mm)
Notes:
1. Liner sections should be continuous without any joints
or seams.
2. Only Flex pipe purchased from Regency
®
may be used
for Flex installations
3. Horizontal vent must be supported every 3 feet.
4. Regency
®
Direct Vent System (Flex) is only approved
for horizontal terminations.
5. Flex system can only be used up to a maximum
continuous vent length of up to 10 feet. If longer runs
are required, rigid pipe must be used.
Horizontal Terminations - Flex Vent 5" x 8"
These venting systems, in combination with the CV60E Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Intertek. The
location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination Locations" section.
Regency
®
Direct Vent (Flex) System Termination Kits include all the parts needed to install the CV60E using a flexible vent.
FPI Kit #
Length Contains:
#946-615
4 Feet
1) 8” flexible liner (Kit length)
2) 5” flexible liner (Kit length)
3) spring spacers
4) thimble
5) AstroCap XL termination cap
6) screws
7) tube of Mill Pac
8) plated screws
9) S.S. screws #8 x 1-1/2” drill point
10) vinyl siding standoff
#946-618
6 Feet
#946-616
10 Feet
*Unit is not exactly as shown.