City Series CV60E-1 |
69
installation
Vent Chart for Power Vent Only
Horizontal Terminations - End of Line Horizontal Vent Chart
Vent Restrictor Position
This negative run is for the end of
line power vent cap only. Do not
run with the inline power vent.
72' (21.95 m) overall length max.
Shown with 5 - 90
0
elbows
Restrictor - Fully Open
72' (21.95 m) overall length max.
Shown with 3 - 90
0
elbows
72' (21.95 m) run (no rise)
Shown with 2 elbows (negative run 72' - 21.95 m)
No vent restrictor required.
318"
238"
138"
Set 0
Fully open
Factory Set
The gas power vent system is designed to allow the installation of a gas appliance when typical vent configurations (shown in this manual) are not
possible.
NO
TES
•
• Rigid pipe is approved for up to 72 feet (22 m).
Rigid pipe is approved for up to 72 feet (22 m).
•
• Flex pipe is approved
Flex pipe is approved for up to 40 feet (12.2 m) using two 20 foot (6.1 m) flex kits (part # 946-756).
for up to 40 feet (12.2 m) using two 20 foot (6.1 m) flex kits (part # 946-756).
•
•
This model co
This model co
mes with a 5" (127 mm) inner and an 8" (203 mm) outer collar which must be reduced to 4" x 6-5/8" (102 mm x 168 mm) in all ap-
mes with a 5" (127 mm) inner and an 8" (203 mm) outer collar which must be reduced to 4" x 6-5/8" (102 mm x 168 mm) in all ap-
plications.
plications.
•
• Must be terminated horizontally. Vertical ter
Must be terminated horizontally. Vertical ter
minations are not permitted.
minations are not permitted.
RIGID PIPE: MUST USE RIGID PIPE ADAPTOR 770-994 AND 946-606 PIPE REDUCER TO 4" X 6 5/8" (102 mm x 168 mm).
FLEX VENT: MUST USE REDUCER 946-758 TO 4" X 6 5/8" (102 mm x 168 mm).
For the complete Power Vent installation, refer the Power Vent System installation instruction in Power vent system Kit
End of Line
Power Vent Kit
# 946-535
IMPOR
TANT
•
•
Maximum total vent length (based on overall length of combined chimney components) = 72' (21.95 m)
Maximum total vent length (based on overall length of combined chimney components) = 72' (21.95 m)
•
•
Maximum total negative vent length = 7' (2.1 m).
Maximum total negative vent length = 7' (2.1 m).
•
•
Do not run positive venting after a negative run.
Do not run positive venting after a negative run.
•
•
Maximum of six - 90° elbows permitted.
Maximum of six - 90° elbows permitted.
•
•
One 90° elbow = two 45° elbows.
One 90° elbow = two 45° elbows.
•
•
Minimum 4' (1.2 m) from the unit prior to terminating.
Minimum 4' (1.2 m) from the unit prior to terminating.