Commissioning
Vacuum spray degassing — 03.11.2014
English — 35
Only displayed if "YES" has been set in the "With softening" menu option.
Is calculated from the difference of the overall water hardness GH
actual
and the target water
hardness GH
target
as defined by the manufacturer specification:
Hardness reduction = GH
actual
-GH
target
l °dH
Enter the value in the controller. Consult the manufacturer information for third-party
products.
Hardness reduction
Only displayed if "YES" has been set in the "With softening" menu option.
The attainable soft water capacity is calculated from the type of softening used and the
specified hardness reduction.
•
Fillsoft I : Soft water capacity
≤
6000/hardness red. l
•
Fillsoft II : Soft water capacity
≤
12000/hardness red. l
Enter the value in the controller. Consult the manufacturer information for third-party
products.
Cap. soft water
Only displayed if "YES" has been set in the "With softening" menu option.
Available soft water capacity.
Remaining cap. soft w.
Only displayed if "YES" has been set in the "With softening" menu option.
Manufacturer specification for the replacement interval of the softening cartridges,
regardless of the calculated soft water capacity. The system displays the "Softening"
message.
Replacement in
Mandatory during commissioning and annual maintenance!
The system must be in manual mode!
Close all inlets to the "PU" vacuum pump.
Vacuum test
yes:
The system starts and automatically executes the test.
"Vacuum OK" is displayed if the test is successful.
"Vacuum Fault" is displayed if the test is failed.
Possible causes for the alarm:
– The vacuum pump is jammed. Start turning the pump at the fan wheel using a
screw driver.
– "DV" degassing valve draws air. Install a new degassing valve.
Check and repair all potential causes and repeat the test.
After the test is successfully concluded, open the inlets to the pump.
no:
The system does not execute a test.
Recommended maintenance message.
Next maintenance
Off: Without
maintenance
recommendation.
001 – 060:
Maintenance recommendation in months.
For the output of messages to the floating contact, see chapter 8.2.4 "Messages" on page
41 .
Floating fault contact
yes:
Output of all messages.
no:
Output of all messages identified with "xxx" ("01", for example).