Installation
22 — English
Vacuum spray degassing — 03.11.2014
6.3.1.2
Make-up line
000173_001_R001
WC
≥ 100
DC
DC
BT
4
1
2
5 6
3
1
"ST" dirt trap
4
Device
2
"BT" mains disconnect receptacle
5
"DC"
degassing line (gas-rich water)
3
"WC" make-up line
6
"DC" degassing line (degassed water)
For water make-up, note the following conditions:
•
For a water make-up via a "BT" mains disconnect receptacle, its bottom edge must be at least 100 mm over the "PU" device pump.
•
Close the connection of the "WC" make-up line when a make-up line is not connected.
– Set the "Levelcontrol" make-up variant at the device controller.
Note!
Avoid a device fault.
– Ensure that manual water make-up to the facility system is possible.
Note!
Use a pressure reducer in the "WC" make-up line if the idle pressure exceeds 6 bar.