Commissioning
34 — English
Vacuum spray degassing — 03.11.2014
Time setting for Continuous degassing.
– For commissioning, we recommend to set the time for continuous degassing
depending on the system volume and the glycol content, see chapter 5 "Technical
data" on page 15 .
Time Continuous. degas.
Switch to the "Make-up" sub-menu.
Make-up
Switch to the next list item.
Make-up
Maximum time for a make-up cycle. Upon expiry of the set time, the system interrupts the
make-up and returns the "Make-up time" fault message.
Max. make-up time
If the set number of make-up cycles is exceeded within 2 hours, the system interrupts the
make-up and returns the "Make-up cycles" fault message.
Max. make-up cycles
This setting is relevant for the actuation of the "CD" 3-ways motor ball valve in make-up
degassing.
> System pressure: Make-up pressure > system pressure
≤
System pressure: Make-up pressure
≤
system pressure
Make-up pressure
yes:
FQIRA+ contact water meter is installed, see chapter 4.6 "Optional equipment and
accessories" on page 14 .
This is the prerequisite for the make-up quantity monitoring and the operation of a
softening system.
With water meter
no:
A contact water meter is not installed (standard).
Only displayed if "YES" has been set in the "With water meter" menu option.
Make-up quantity
OK Delete
meter:
yes:
The displayed make-up quantity is set to 0.
no: The
displayed
water
quantity is retained.
Only displayed if "YES" has been set in the "With water meter" menu option.
When the set quantity is exceeded, the system interrupts the make-up process and returns
the error message "Max. make-up quantity exceeded".
Max. make-up quantity
Only displayed if "YES" has been set in the "With water meter" menu option.
With softening
yes:
The system offers more queries regarding the softening process.
no:
The system does not offer more queries regarding the softening process.
Only displayed if "YES" has been set in the "With softening" menu option.
Lock make-up?
yes:
The system stops the make-up process when the set soft water capacity is exceeded.
no:
The system does not stop the make-up process. The system displays the "Softening"
message.