Troubleshooting
Technical dept. - All rights reserved - Reproduction prohibited
7.
TROUBLESHOOTING
The following paragraph was written to provide a handy, quick guide to our customers to understand
problems which could occur when using the TECNIKA.
No.
Fault
Cause
Repair method
1.
Low temperatures in the
heated rooms
Insufficient boiler heat
output
Increase fuel loading frequency
and/or increase amount of loaded
fuel
Adjust boiler heat output
Check humidity content in wood logs
and replace with drier fuel if needed
Low set point temperature of
the boiler operating
thermostat
The set point of the boiler operating
thermostat needs to be raised (up to
90
o
C)
Low temperature set point of
the remote room thermostat
(where connected)
The room thermostat set point needs
to be raised
2.
High temperatures in the
heated rooms
High set point temperature of
the boiler operating
thermostat
The set point of the boiler operating
thermostat needs to be decreased (it
is advisable to keep it over 65
o
C)
High temperature set point of
the remote room thermostat
(where connected)
The room thermostat set point needs
to be decreased
High heat output of boiler
Decrease fuel loading frequency
and/or decrease amount of loaded
fuel
3.
Emergency boiler
overheating
No heat consumption or
incorrect adjustment of the
boiler parameters, or poor
functioning of the heating
system
Check correct operation of the
heating system and adjust the
operating parameters of the boiler
and/or of the heating system control
valves if needed.
These interventions
must be carried out by an authorised
technician. When the boiler has
cooled down to ambient temperature
and the cause of the boiler
overheating has been remedied,
unscrew the protection cap from the
emergency overheating thermostat
and press the stem until the
thermostat is reset, then screw the
cap back on. Turn the “POWER” main
switch on and off and then restart
the boiler.