5.3.1
Roof outlet along a traditional flue pipe
The flue smoke can also be discharged using an existing traditional flue pipe provided it is compliant to
standards (see UNI 10683).
Here is a brief list of the main characteristics highlighted in the standard that distinguish a good chimney:
- Suitable insulation and lagging especially in the external section exposed to the atmosphere;
- Constant internal cross-section (there must not be any narrower sections);
- Made with material resistant to high temperatures, to the action of the products of combustion and to the
corrosive action of any condensation that may form;
- Prevalently vertical arrangement with deviations from the axis of no more than 45°;
It is compulsory to plan a chamber for the collection of solid material and/or any condensation, which can be
inspected through an airtight door.
It is compulsory for you to observe the provisions of standards UNI 9615 and 9731 for the sizing of the
chimney cross-section and in any case that you avoid installing ducts with a cross-section of less than
150 mm.
In the case of larger cross-sections, it may be necessary to insert a steel duct inside the masonry one.
Direct wall discharge is not permitted.
The steel pipe must be suitably insulated with material which is resistant
to high temperatures and sealed off from the external chimney.
Soot tray accessible for
inspection with possible
condensation discharge