red
TECNIKA 28-35
USE AND INSTALLATION MANUAL
Chapter
5
page 30
Operation
Technical dept. - All rights reserved - Reproduction prohibited
Operation thermostat
- Assigns the set point of the water circulating the boiler. The
combustion gas fan of the boiler will run until this set point is reached and supplies thermal
energy to the heating system. The boiler will switch to stand-by mode.
Combustion gas thermostat
- Assigns the combustion gas temperature set point. The
boiler combustion gas fan does not work at temperatures lower than the set point of this
thermometer and combustion gases will not be extracted by the fan. Consequently, the
remaining combustion residues will not be consumed if they remain in the fuel hopper of the
boiler only.
Temperature pressure gauge
- This indicates the operating temperature of the water
circulating in the heat exchanger sleeve of the boiler in addition to water overpressure.
"
START
" switch - This sends the "START/STOP" signal to the boiler combustion gas fan
which will run at nominal heat output (ON) or switch to stand-by mode (OFF).
"
START
" warning light - This indicates the "START/STOP" state signal to the boiler
combustion gas fan.
"Alarm 1" warning light - Overheat emergency
- This indicates an overheating
emergency of the boiler caused by activation of the emergency thermostat. In case of
activation, cool the appliance, check and repair the cause of the emergency situation.
Finally, reset the emergency thermostat.
“Alarm 2" warning light
- (
optional)
- This indicates the heat exchanger state - If the
combustion gas temperature is higher than given levels the warning light will come on and
ashes must be cleaned.
The following control devices are arranged on the rear part of the boiler interface control panel:
Figure 5.1.2
Interface control panel provided with "Tecnika" hot water boiler control and operation devices
-
rear view
Main "
POWER
" switch - Turns main power supply of the boiler ON and OFF.
Emergency thermostat
- Protects the boiler from exceeding emergency temperature
levels and overheating. This thermostat is calibrated at the factory to cut off the power
supply of the appliance at a water temperature higher than 95
o
C.
POWER
switch
Emergency
thermostat
Wire
duct
elements