red
PRACTIKA 28-33
USE AND INSTALLATION MANUAL
Chapter 9
page 50
Menu structure
Technical dept. - All rights reserved - Reproduction prohibited
9.2.13.
Start Pump
This function manually starts the circulation pump to run the circulation test on the system.
9.3.
Adjusting the water temperature in the boiler
The water temperature is displayed in real time on the start screenshot of the control panel. The boiler set
point (TH
2
O) is the desired temperature of the water in the boiler. When this temperature is reached, the
boiler diminishes its performance to avoid overheating. The default temperature set is 65°C but it can be set
between 50°C and 80°C. If the user wishes to change this value, (s)he can do so as follows:
press key D to enter the settings screenshot.
Press key F for 1 second until the parameter setting is shown.
Press F and C to change the value, and confirm with D.
9.4.
Adjusting the maximum flame level
The maximum flame level is the maximum level the boiler can reach during modulation. If for instance the
setting is Fire: 3, when the boiler modulates up, it will never exceeds the flame level 3. If the user wishes to
change this value, (s)he can do so as follows:
press key D to enter the settings screenshot.
Press key E for 1 second until the parameter setting is shown.
Press F and C to change the value, and confirm with D.
Esc Ok
- Fire +
Fire:5
TH2O:75°C
65°C H2O 21.04
OFF
Esc Ok
- Fire +
Esc 65°C Set
- Water temp. +
Esc 70°C Ok
- Water temp. +
Fire:5
TH2O:75°C
65°C H2O 21.04
OFF