PELLET STOVES
Chapter 2
red
INSTALLATION AND USE MANUAL
page
14
Theoretical notions for installation
Technical service - Rights reserved - Reproduction prohibited
Pipes and unions with suitable gaskets must always
be used, to guarantee a hermetic seal (class P1,
reference standard EN 1856-2).
All sections of the smoke duct must be inspectable and
removable to enable periodic internal cleaning. Tee
connectors with inspection caps should be used.
Position the stove bearing in mind all the instructions and
considerations above.
IMPORTANT!
All 90 degree changes of direction in the flue pipe
must be fitted with suitable tee connectors to allow
the possibility of inspection. (see accessories for
pellet stove)
It is absolutely prohibited to fit a grille on the end of
the discharge pipe, because it could lead to poor
running of the stove.
FOR CONNECTION TO THE FLUE PIPE, NOT MORE
THAN 2-3 METRES OF HORIZONTAL PIPE MUST BE
USED AND NOT MORE THAN THREE 90° CURVES
MUST BE USED
IT IS ALSO ADVISABLE NOT TO EXCEED 6 METRES IN
LENGTH WITH THE PIPE Ø 80 mm
Example of pellet stove installation