Parameter explanations V2.1_V2.6
2
IRA_B8_EN_2V2_REC_102-020401137
37/ 56
→ Interlock
Configuration for interlock operation.
▪ It is possible to operate the system with sensors between
the doors or without sensors with interlock sequential con-
trol.
Parameter
Default value
Input → AUX10_IN
S_AUS
Input → AUX11_IN
SEA
Input → AUX12_IN
SFS_IN
Output → AUX10_OUT
SAA
Output → AUX11_OUT
SAMP
Output → AUX12_OUT
SFS_OUT
→ Pharmacy
Configuration for pharmacy control.
▪ The door is opened and closed by an on/off switch.
▪ The movements occur at reduced speed, as no sensors
are active (triggering and safety).
▪ NSK/SÖK is not active!
Parameter
Default value
Input → AUX10_IN
APS locking contact
Input → AUX11_IN
APS opening
Output → AUX10_OUT
APS signal light
→ I/O-Set 1
Set of parameters 1
Parameter
Default value
Output → AUX11_OUT
Alarm output
Output → AUX12_OUT
Open
Output → AUX13_OUT
Closed
Output → AUX14_OUT
Emergency stop / opening
Output → AUX15_OUT
ELS error
Output → AUX16_OUT
Battery error
Output → AUX17_OUT
Locking error
Output → AUX18_OUT
Power failure
Output → AUX19_OUT
OM Automatic
Output → AUX1A_OUT
Reduced opening
Output → AUX1B_OUT
OM Continuously open
Output → AUX1C_OUT
BA One-Way
Output → AUX1D_OUT
BA Locked
Summary of Contents for system 20
Page 1: ...record system 20 B8 Parameter explanations Translation of the original manual ...
Page 48: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 48 56 ...
Page 50: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 50 56 ...
Page 52: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 52 56 ...
Page 54: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 54 56 ...
Page 56: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 56 56 ...