![Real Flame EXURO IO1000 Installation & Operating Manual Download Page 16](http://html1.mh-extra.com/html/real-flame/exuro-io1000/exuro-io1000_installation-and-operating-manual_1425123016.webp)
INSTALLATION
(continued)
16
Laying Gas Pipe
Gas pipe should be sized as per the requirements of AS5601/AG601-2000. The pipe sizing must
be sufficient to deliver the following volume of gas to the heater with all other gas appliances in
the home running at the same time;
IO1000 Natural Gas = 49 Mj/hr
IO1000 Propane = 40 Mj/hr
IO1000 ULPG = 40 Mj/hr
It is highly recommended to install an easily accessible isolating shut off valve (ball valve) along
the gas line to the IO1000 unit which should be easily accessible to the user.
This fire has been supplied with a ½” pipe connected through a short 45° flare nut inlet connection
to make the gas supply easy and safe. Solid pipe should be run to the inside lower left hand side
of the fire. Insert the supplied rubber plug and cut it as shown below to allow the gas pipe and the
electrical cable to pass through, keeping the plug as air-tight as possible.
Gas Pipe Entry Point
Any flexible pipe should be attached to the copper supply pipe and joint tested to ensure gas
tightness, an isolating valve is recommended for this purpose.
Before each use of the appliance the hose assembly connecting the appliance to the gas supply
must be inspected. If there is evidence of excessive abrasion or wear, or if the hose is damaged,
then the hose assembly must be replaced before the appliance is operated.
The gas hose should be properly located away from pathways or areas where the hose may be
subject to accidental damage.
Summary of Contents for EXURO IO1000
Page 22: ...ELECTRICAL SCHEMATIC 22...
Page 23: ...EXPLODED VIEW 23...