1. Introduction to RPCM
1. Introduction to RPCM
1.1. Main Functions
RPCM stands for Resilient Power Control Module. It was designed in response to market demand
for managed and switched PDU that could protect individual outlets from short circuits.
During its development, we decided to add features, such as power metering and proper ground-
ing diagnostics. As a result, RPCM has the following characteristics:
Inputs
:
2 x 76А -48VDC (42-58VDC) (ATS), max. current 76А for RPCM DC ATS 76A.
1 x 232A -48VDC (42-58VDC), max. current 232А for RPCM DC 232A.
Outlets
:
10 outlets, designed for a current of 30A (with a 4 mm
2
cross section); 24A (with a cross sec-
tion of 2.5 mm
2
wires).
Overconsumption protection with individual configuration of each outlet for alarm and turn off
threshold.
Proper grounding indication.
Configuration of activation sequence and delays;
Priority configuration for outlets to turn off in case of input consumption in exceed input of con-
sumption limit.
Remote control via web interface, SSH, SNMP v1/v2c/v3, REST API.
Main applications of RPCM include:
increasing electrical safety;
increasing fire safety;
ensuring continuous operation;
monitoring and saving energy;
management IT infrastructure with flexibility.
5