background image

Finned copper tube gas boilers & water heaters – Boiler Manual

17

DOMESTIC WATER SUPPLY PIPING

  Proper controls must be used to prevent water sup-

plied for domestic use from exceeding 

130°F

54°C

 

or a scald injury will occur! When higher water tem-

peratures are required for appliances such as a dish-

washer, a mixing valve or some other tempering means 

must be installed. Households with small children may 

require water temperatures less than 

120°F

49°C

Local codes must be complied with!

General Piping Requirements 

Ensure  that  the  water  heater  is  equipped  with  bronze 

headers.

 Piping and components connected to the water heater 

must be suitable for use with potable water. The water heater must 

not be connected to any heating system piping or components 

previously used with a non-potable water heating appliance. No 

toxic chemicals, such as those used for boiler treatment, are to be 

introduced into the potable water used for space heating. If a hot 

water storage tank is used in the system it must be equipped with 

a temperature and pressure relief valve that complies with ANSI 

Z21.22 or CAN-4.4 and CAN-4.6.

  The storage tank must be located as close to the water 

heater as possible to prevent excessive head loss which 

will reduce flow.

Water Chemistry

The required temperature rise across the water heater is based on 

water having a hardness between 8 and 18 grains per gallon with 

a level of dissolved solids not exceeding 350 ppm. Water having a 

hardness less than 8 grains can cause excessive corrosion of the 

heat exchanger. Water that has a hardness greater than 18 grains 

per gallon and/or a level of dissolved solids exceeding 350 ppm 

will require a recalculation of the pump size and temperature rise. 

A cupro-nickel heat exchanger may also be required. The manufac-

turer should be consulted when these water conditions are  

encountered. See Table 9.

  The maximum allowable flow rate through a Futera III 

water heater is 97 GPM, 6.1 L/s on 500 through 1000 

models and 136 GPM, 8.9 L/s for 1250 through 2000 

models. The cupro-nickel heat exchanger allows for  

108 GPM, 6.8 L/s on 500 through 1000 models and  

151 GPM, 9.5 L/s on 1250 through 2000 models, see  

Table 8B.

RBI water heaters are designed to run scale free. Due to the extreme 

variables of water conditions world wide it is necessary to  

consider pH values and water hardness in relationship to scaling. 

It is crucial to consider these two variables when making heat  

exchanger and pump selections. If local water conditions are extreme, 

follow the guidelines in the Heat Exchanger Selection (Table 9) 

and the Pumping Performance (Table 10). Scale free operation 

can be achieved by using water with a hardness between 8 and 18 

and by maintaining the pH between 5 and 9. Follow the conditions 

listed under NORMAL in the table. In some areas of the country 

additional precautions must be observed due to unusual charac-

teristics of the local water supply. Call the nearest RBI representa-

tive for details. 

To properly size the pump a grain hardness and pH test  

must be taken at the installation site before the order is placed. 

Proper pump sizing will improve heater performance and help 

ensure heater longevity.

Expansion Tank 

An expansion tank or other means to control thermal expansion 

must be installed in the water heating system if back flow preven-

tion devices are installed.

Pump Requirements 

This low-mass water heater requires a continuous mini-mum water 

flow for proper operation. The low water flow switch provided for 

this unit will shut down the water heater if flow falls below the 

required minimum level. Table 10 provides the heat exchanger pres-

sure drop chart and temperature rise table. 

The temperature rise 

across the water heater must never exceed 35°F, 19.4°C

.

Cold Water Supply

The cold water supply must be piped to the water heater’s outlet 

piping between the water heater and the hot water storage tank. 

This will prevent untempered water from entering the water heater, 

see the Temperature Rise Control section below. Two typical water 

heating systems are shown in Figures 16 & 17.

Temperature Rise Control 

Water returned to the water heater inlet must not be less than 

125°F

52°C

 or excessive condensation of the products of combustion will 

damage the water heater voiding the warranty. The method outlined 

below can be employed to prevent this condition from occurring. 

A balancing valve should be installed on the outlet side of  

the water heater for purposes of adjusting the flow rate through 

the heat exchanger. Thermometers are installed on both the inlet 

and outlet of the water heater for determining the temperature rise 

through the unit. 

The proper velocity through the water heater must be maintained 

in accordance with Table 10 for efficient operation and long life.  

If the temperature rise through the water heater is lower than 

recommended the water velocity is too high. Premature erosion of 

the heat exchanger will occur. Conversely, if the temperature rise 

is higher than recommended in Table 10 the flow rate is too low. 

Scaling and softening of the heat exchanger will occur.

Thermostatic Mixing Valve – Water Above 140°F

,

 60°C

 Water 

can be stored at temperatures above 

140°F

60°C

 provided that a 

thermostatically controlled mixing valve is used to temper the hot 

water to an acceptable temperature before it’s supplied for domestic 

use. 

The mixing valve MUST be set to prevent a scald injury from 

occurring, see the caution against scalding.
Storage of water for domestic use above 

140°F

60°C

 will provide 

an increased quantity of tempered water and help prevent the growth 

of water born bacteria. 

Summary of Contents for Futera II Modulation

Page 1: ...g construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The...

Page 2: ...it can cause excessive amounts of carbon monoxide resulting in severe personal injury or death DESIGNED AND TESTED ACCORDING TO A S M E BOILER AND PRESSURE VESSEL CODE SECTION IV FOR A MAXIMUM ALLOWAB...

Page 3: ...in mm Top 6 153 30 762 Back 6 153 24 610 Left Side 6 153 12 306 Right Side 6 153 12 306 Front 6 153 30 762 2 An optimum site will be level central to the piping system close to a chimney or outside w...

Page 4: ...within 12 in 305 mm of but not less than 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the bottom of the enclosure Where...

Page 5: ...sized to provide a negative draft of 03 in 0 8 mm to 1 in 2 5 mm W C at the flue outlet Common positive pressure vent systems are not to be used Improper installation can result in excessive levels of...

Page 6: ...The bottom of the vent terminal s shall be located at least 5 ft 1 5 m above the air intake terminal s unless there is a minimum 5 ft 1 5 m horizontal separation between them Avoid terminal locations...

Page 7: ...t and combustion air ter minals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds Incoldclimates double wallorinsulatedinletpipe recomme...

Page 8: ...s Boiler Manual 8 Figure 3 Vertical Air Intake and Venting for a Direct Vent System Category IV Figure 4 Combination Direct Vent Systems Category IV 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1...

Page 9: ...y into a listed metal chimney system Figures 7 9 Thechimneymustprovideanegativepressurenotgreaterthan0 10 in 2 5 mm W C at the boiler water heater flue collar with the unit running The Futera III when...

Page 10: ...at 3 ft 0 9 m intervals with overhead hangers Use a single wall stainless steel vent pipe the same diameter as the flue collar to connect the boiler water heater to a masonry chimney When using a list...

Page 11: ...e 9 Vertical Venting Using a Lined Masonry Chimney Category II Figure 11 Multiple Outdoor Units Figure 8 Vertical Venting Using a Lined Masonry Chimney Category I Figure 10 Outdoor Venting Category IV...

Page 12: ...nstall s et les autres espaces du b timent Mettre en marche les s cheuses tous les appareils non raccord s au syst me d vacuation commun et tous les ventilateurs d extraction comme les hottes de cuisi...

Page 13: ...pe of valve between the boiler waterheaterandthereliefvalveoranexplosioncausing extensive property damage severe personal injury or death may occur Flow Switch The flow switch supplied with the boiler...

Page 14: ...heater for proper wiring connections Expansion Tank Air Separator An expansion tank or other means to control thermal expansion must be installed in the heating system An expansion tank must be insta...

Page 15: ...urn temperature 7 For HeatNet operation a sensor is required and installed at a minimum of 12 from primary loop tee supplied Notice These drawings show suggested piping configuration and valving Check...

Page 16: ...rs furnished with factory mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplied 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow...

Page 17: ...nd by maintaining the pH between 5 and 9 Follow the conditions listed under NORMAL in the table In some areas of the country additional precautions must be observed due to unusual charac teristics of...

Page 18: ...Finned copper tube gas boilers water heaters Boiler Manual 18 Table 9 Futera III Heat Exchanger Selection Graph Table 10 Futera III Pumping Performance Requirement...

Page 19: ...ed pump max pipe length 30 ft total 6 90 elbows full pipe size 5 CAUTION MEASURE WATER HARDNESS AND pH AT JOB SITE 6 The pH and water hardness must be measured before selecting heat exchanger and pump...

Page 20: ...at the bottom of the vertical section of the gas supply pipe upstream of the gas controls A ground joint union should be installed between the boiler gas controls and the supply piping Each of these i...

Page 21: ...s installed oudoors The wire size must be compatible with the total amp draw of the circuit Refer to the wiring diagram supplied with the boiler water heater for proper wiring connections and boiler f...

Page 22: ...il a t plong dans l eau m me partiellement Faitesinspecterl appareilparuntecnicienqualifi et remplacez toute partie du syst me de contr le et toute com mande qui ont t plong s dans l eau Operating Ins...

Page 23: ...Nat Gas Category II and IV Firing rate 500 750 1000 1250 1500 1750 2000 Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc 100 2 2 4...

Page 24: ...off all electric power to the boiler if service is to be performed 3 Close the manual main and pilot gas shut off valves COMMENT COUPER L ADMISSION DE GAZ DE L APAREIL 1 R glez le thermostat la temp...

Page 25: ...when the boiler is firing at full rate Low gas pressure could indicate undersized gas line or insufficient gas supply Static and operating gas pressure required at the gas valve inlet is between 2 W...

Page 26: ...Finned copper tube gas boilers water heaters Boiler Manual 26 RBI FIELD WIRING TO HEATNET BOARD Figure 22 RBI Field Wiring to HeatNet Board Board Revision 3 0 and greater...

Page 27: ...n be used to control HeatNet equipped boilers Method 1 A 4 20mA signal can be used to directly modulate each boiler from a remote panel or building management system On multiple boiler installations t...

Page 28: ...y will also list faults should the unit fail to operate An explanation of each status message and fault can be located in HeatNet Control Manual under status screen fault display section STATUS SCREEN...

Page 29: ...ock is located on J11B SPARE 4 FAULT SYSTEM SET 160 F INTERLOCK SPARE 4 FLOW SWITCH ERROR Once the FIII series boiler receives a call for heat it closes the circulator pump relay It then waits 10 seco...

Page 30: ...ET 160 F OPEN OUTSIDE SENSOR SHORTED SENSOR If the shorted sensor fault is displayed thesensorinthepositionreportedwasoriginallydetected but has since shorted The boiler will shut down on any SHORTED...

Page 31: ...osits indicate condensation due to low return water temperatures In either case the heat exchanger must be cleaned thoroughly and the problem resolved before the boiler water heater is returned to ser...

Page 32: ...qualified service technician to have it inspected NEVER try to clean or repair the relief valve If the valve fails to operate properly have it replaced 5 Theaquastathighlimitcontrolsthemaximumwaterte...

Page 33: ...entify which interlock has tripped Reset the Interlock or check for disconnected wiring or shorts The Air Pressure from UV Sensor interlock if displayed will allow the boiler to function but it needs...

Page 34: ...Finned copper tube gas boilers water heaters Boiler Manual 34 Figure 25 Exploded View REPAIR PARTS...

Page 35: ...Finned copper tube gas boilers water heaters Boiler Manual 35 REPAIR PARTS CONTINUED RIOM 74 REV E...

Page 36: ...4 2 2 2 2 2 2 2 19 Flange 1 Outlet 11 0228 1 1 1 1 Flange 1 1 2 Outlet 11 0229 1 1 1 NS Orifice Gasket 06 0022 1 1 1 1 1 1 1 NS Gas Injectors NG 10 1009 1 1 1 1 Gas Injectors NG 10 1002 1 1 1 Gas Inje...

Page 37: ...1 1 1 1 Tridicator 75 160 psi 13 0305 1 1 1 1 1 1 1 46 Heat Exchanger Assembly Copper 70 2515 1R 1 Cast Iron prior to 0209 must replace 70 2516 1R 1 combustion chamber top panel 36 70 2517 1R 1 70 25...

Page 38: ...2 2 2 NS 10K Temperature Sensor 14 0325 3 3 3 3 3 3 3 50 Transformer 50 VA 15 0007 1 1 1 1 1 1 1 51 Purge Timer ST7800 16 0007 1 1 1 1 1 1 1 52 Spark Generator Q652B 16 0036 1 1 1 1 1 1 1 53 Flame Saf...

Page 39: ...0102 1 1 1 1 1 1 1 81 Pilot Orifice 052 NG 10 0140 1 1 1 1 1 1 1 Pilot Orifice 040 LP 10 0139 1 1 1 1 1 1 1 82 Mini Peeper C7027A 16 0009 1 1 1 1 1 1 1 83 Spark Plate Gasket 06 0102 1 1 1 06 0037 1 1...

Page 40: ...he electrical panel Disable any external call for heat and toggle the remote local switch to REMOTE 1 Toggle the LOW FIRE switch to cycle the boiler then hold at trial for pilot ignition 2 Set pressur...

Page 41: ...TWEEN THE HEATER INLET AND OUTLET IS CRITICAL TO PROPER FLOW BEFORE YOU LEAVE THE JOBSITE YOU MUST RECORD THE DELTA T THIS READING SHOULD NOT EXCEED 35 F 19 4 C NOR BE LOWER THAN 20 F 11 2 C DELTA T C...

Page 42: ...the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS g INSP...

Page 43: ...ubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty See Installation Instructions for proper pump performance Chemical corrosion no corrosive chemica...

Page 44: ...right 2014 Mestek Inc 260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782 www rbiwate...

Reviews: