background image

Finned copper tube gas boilers & water heaters – Boiler Manual

4

  Combustion air contaminated with fluorocarbons 

or other halogenated compounds such as cleaning 

solvents and refrigerants will result in the formation 

of acids in the combustion chamber. These acids will 

cause premature failure of the boiler/water heater 

voiding the warranty!

  If the boiler/water heater is operated while the building 

is under construction it MUST be protected from 

wood, concrete, sheet rock and other types of dust. 

Failure to properly protect the unit from construction 

dust will damage the unit voiding the warranty!

Buildings will require the installation of a fresh air duct or other 

means of providing make-up air if the intake air option isn’t used. 

Any building utilizing other gas burning appliances, a fireplace, wood 

stove or any type of exhaust fan must be checked for adequate 

combustion air when all of these devices are in operation at one 

time. Sizing of an outside air duct must be done to meet the 

requirements of all such devices.

 

Never operate the Futera III in an environment 

subjected to a negative pressure unless it is Direct 

Vented.  Failure to comply with this warning can result 

in excessive levels of carbon monoxide causing severe 

personal injury or death!

All Air From Inside The Building 

If the Futera III is to be located in a confined space, the minimum 

clearances listed in Table 1 must be maintained between it and any 

combustible construction. When installed in a confined space 

without the intake air option,

 Figures 5, 6 and 7, two permanent 

openings communicating with an additional room(s) are required. 

The combined volume of these spaces must have sufficient volume 

to meet the criteria for an unconfined space. The total air 

requirements of all gas utilization equipment, fireplaces, wood stoves 

or any type of exhaust fan must be considered when making this 

determination. Each opening must have a minimum free area of  

1 in

2

/1000 Btu/hr

2200 mm

2

/kW

 based on the total input rating 

of ALL gas utilization equipment in the confined area. Each opening 

must be no less than 

100 in

2

64,516 mm

2

 in size. The upper 

opening must be within 

12 in

,

 305 mm

 of, but not less than 

3 in

 

76 mm

 from, the top of the enclosure. The bottom opening must 

be within 

12 in

305 mm

 of, but not less than 

3 in

76 mm

 from, 

the bottom of the enclosure.

All Air From Outside The Building 

When installed in a confined space 

without utilizing the intake 

air option

 two permanent openings communicating directly with, 

or by ducts to, the outdoors or spaces that freely communicate 

with the outdoors must be present. The upper opening must be 

within 

12 in

305 mm

 of, but not less than 

3 in

76 mm

 from, the 

top of the enclosure. The bottom opening must be within 

12 in

305 mm

 of, but not less than 

3 in

76 mm

 from, the bottom of 

the enclosure.

Where directly communicating with the outdoors or communi-

cating with the outdoors through vertical ducts, each opening shall 

have a minimum free area of 

1 in

2

/4000 Btu/hr

550 mm

2

/kW

 

of the total input rating of all of the equipment in the enclosure.

Where communicating with the outdoors through horizontal  

ducts, each opening shall have a minimum free area of 

1 in

2

2000 Btu/hr

1100 mm

2

/kW

 of the total input rating of all of 

the equipment in the enclosure. 

When ducts are used, they must have the same cross-sectional area 

as the free area of the opening to which they connect.

When calculating the free area necessary to meet the make-up air 

requirements of the enclosure, consideration must be given to the 

blockage effects of louvers, grills and screens. Screens must have a 

minimum mesh size of 

1/4 in

6.4 mm

. If the free area through a 

louver or grill is not known, ducts should be sized per Table 2.

Canadian installations must comply with CSA B149.1 when 

air 

supply

 is provided by natural air flow from the outdoors for 

natural 

draf

t, partial fan-assisted, fan-assisted, or power draft-assisted 

burners

, there shall be a permanent 

air supply

 opening(s) having 

a cross-sectional area of not less than 

1 in

2

 per

 

7,000  Btuh

  

(310 mm

2

 per kW)

 up to 

and including

 

1 million Btuh,

 plus 

1 in

2

  per  14,000  Btuh

 

(155 mm

2

 per kW)

 

in excess of

  

1 million Btuh

Table 2  Make-up Air Louver Sizing

Required Cross Sectional Area

Input

(MBH)

1/4 in 

6.4 mm

Wire Screen

75% Free Area

Metal Louvers

25% Free Area

Wooden Louvers

 

in

2

cm

2

in

2

cm

2

in

2

cm

2

  500

125

  

806

167

1077

  500    

3226

  750

187

1206

250

1613

  750   

 4839

1000

250

1613

333

2148

1000   

 6452

1250

313

2019

416

2684

1250    

8065

1500

375

2419

500

3226

1500    

9677

1750

437

2819

583

3761

1750

11,290

1999

500

3226

667

4303

2000

12,900

Intake Air Option – General Guidelines 

This configuration provides combustion air directly to the boiler/

water heater’s air intake adapter using a dedicated pipe when using 

the direct vent option. Combustion air can be drawn in horizontally 

through the same outside wall which terminates the exhaust gases 

or vertically through the roof, see Figures 1, 2, 3 & 4.

 

Common intake air systems may be used provided the 

common duct is sized properly. An intake combustion 

air damper should be installed if the common vent 

option is used in the intake air pipe of each heater. 

Improper installation can result in excessive levels of 

carbon monoxide which can cause severe personal 

injury or death!

Single wall galvanized smoke pipe, single wall aluminum pipe, 

flexible aluminum pipe, PVC or CPVC pipe can be used for the 

intake air pipe. It must be sized per Table 3.

Summary of Contents for Futera II Modulation

Page 1: ...g construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The...

Page 2: ...it can cause excessive amounts of carbon monoxide resulting in severe personal injury or death DESIGNED AND TESTED ACCORDING TO A S M E BOILER AND PRESSURE VESSEL CODE SECTION IV FOR A MAXIMUM ALLOWAB...

Page 3: ...in mm Top 6 153 30 762 Back 6 153 24 610 Left Side 6 153 12 306 Right Side 6 153 12 306 Front 6 153 30 762 2 An optimum site will be level central to the piping system close to a chimney or outside w...

Page 4: ...within 12 in 305 mm of but not less than 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the bottom of the enclosure Where...

Page 5: ...sized to provide a negative draft of 03 in 0 8 mm to 1 in 2 5 mm W C at the flue outlet Common positive pressure vent systems are not to be used Improper installation can result in excessive levels of...

Page 6: ...The bottom of the vent terminal s shall be located at least 5 ft 1 5 m above the air intake terminal s unless there is a minimum 5 ft 1 5 m horizontal separation between them Avoid terminal locations...

Page 7: ...t and combustion air ter minals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds Incoldclimates double wallorinsulatedinletpipe recomme...

Page 8: ...s Boiler Manual 8 Figure 3 Vertical Air Intake and Venting for a Direct Vent System Category IV Figure 4 Combination Direct Vent Systems Category IV 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1...

Page 9: ...y into a listed metal chimney system Figures 7 9 Thechimneymustprovideanegativepressurenotgreaterthan0 10 in 2 5 mm W C at the boiler water heater flue collar with the unit running The Futera III when...

Page 10: ...at 3 ft 0 9 m intervals with overhead hangers Use a single wall stainless steel vent pipe the same diameter as the flue collar to connect the boiler water heater to a masonry chimney When using a list...

Page 11: ...e 9 Vertical Venting Using a Lined Masonry Chimney Category II Figure 11 Multiple Outdoor Units Figure 8 Vertical Venting Using a Lined Masonry Chimney Category I Figure 10 Outdoor Venting Category IV...

Page 12: ...nstall s et les autres espaces du b timent Mettre en marche les s cheuses tous les appareils non raccord s au syst me d vacuation commun et tous les ventilateurs d extraction comme les hottes de cuisi...

Page 13: ...pe of valve between the boiler waterheaterandthereliefvalveoranexplosioncausing extensive property damage severe personal injury or death may occur Flow Switch The flow switch supplied with the boiler...

Page 14: ...heater for proper wiring connections Expansion Tank Air Separator An expansion tank or other means to control thermal expansion must be installed in the heating system An expansion tank must be insta...

Page 15: ...urn temperature 7 For HeatNet operation a sensor is required and installed at a minimum of 12 from primary loop tee supplied Notice These drawings show suggested piping configuration and valving Check...

Page 16: ...rs furnished with factory mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplied 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow...

Page 17: ...nd by maintaining the pH between 5 and 9 Follow the conditions listed under NORMAL in the table In some areas of the country additional precautions must be observed due to unusual charac teristics of...

Page 18: ...Finned copper tube gas boilers water heaters Boiler Manual 18 Table 9 Futera III Heat Exchanger Selection Graph Table 10 Futera III Pumping Performance Requirement...

Page 19: ...ed pump max pipe length 30 ft total 6 90 elbows full pipe size 5 CAUTION MEASURE WATER HARDNESS AND pH AT JOB SITE 6 The pH and water hardness must be measured before selecting heat exchanger and pump...

Page 20: ...at the bottom of the vertical section of the gas supply pipe upstream of the gas controls A ground joint union should be installed between the boiler gas controls and the supply piping Each of these i...

Page 21: ...s installed oudoors The wire size must be compatible with the total amp draw of the circuit Refer to the wiring diagram supplied with the boiler water heater for proper wiring connections and boiler f...

Page 22: ...il a t plong dans l eau m me partiellement Faitesinspecterl appareilparuntecnicienqualifi et remplacez toute partie du syst me de contr le et toute com mande qui ont t plong s dans l eau Operating Ins...

Page 23: ...Nat Gas Category II and IV Firing rate 500 750 1000 1250 1500 1750 2000 Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc 100 2 2 4...

Page 24: ...off all electric power to the boiler if service is to be performed 3 Close the manual main and pilot gas shut off valves COMMENT COUPER L ADMISSION DE GAZ DE L APAREIL 1 R glez le thermostat la temp...

Page 25: ...when the boiler is firing at full rate Low gas pressure could indicate undersized gas line or insufficient gas supply Static and operating gas pressure required at the gas valve inlet is between 2 W...

Page 26: ...Finned copper tube gas boilers water heaters Boiler Manual 26 RBI FIELD WIRING TO HEATNET BOARD Figure 22 RBI Field Wiring to HeatNet Board Board Revision 3 0 and greater...

Page 27: ...n be used to control HeatNet equipped boilers Method 1 A 4 20mA signal can be used to directly modulate each boiler from a remote panel or building management system On multiple boiler installations t...

Page 28: ...y will also list faults should the unit fail to operate An explanation of each status message and fault can be located in HeatNet Control Manual under status screen fault display section STATUS SCREEN...

Page 29: ...ock is located on J11B SPARE 4 FAULT SYSTEM SET 160 F INTERLOCK SPARE 4 FLOW SWITCH ERROR Once the FIII series boiler receives a call for heat it closes the circulator pump relay It then waits 10 seco...

Page 30: ...ET 160 F OPEN OUTSIDE SENSOR SHORTED SENSOR If the shorted sensor fault is displayed thesensorinthepositionreportedwasoriginallydetected but has since shorted The boiler will shut down on any SHORTED...

Page 31: ...osits indicate condensation due to low return water temperatures In either case the heat exchanger must be cleaned thoroughly and the problem resolved before the boiler water heater is returned to ser...

Page 32: ...qualified service technician to have it inspected NEVER try to clean or repair the relief valve If the valve fails to operate properly have it replaced 5 Theaquastathighlimitcontrolsthemaximumwaterte...

Page 33: ...entify which interlock has tripped Reset the Interlock or check for disconnected wiring or shorts The Air Pressure from UV Sensor interlock if displayed will allow the boiler to function but it needs...

Page 34: ...Finned copper tube gas boilers water heaters Boiler Manual 34 Figure 25 Exploded View REPAIR PARTS...

Page 35: ...Finned copper tube gas boilers water heaters Boiler Manual 35 REPAIR PARTS CONTINUED RIOM 74 REV E...

Page 36: ...4 2 2 2 2 2 2 2 19 Flange 1 Outlet 11 0228 1 1 1 1 Flange 1 1 2 Outlet 11 0229 1 1 1 NS Orifice Gasket 06 0022 1 1 1 1 1 1 1 NS Gas Injectors NG 10 1009 1 1 1 1 Gas Injectors NG 10 1002 1 1 1 Gas Inje...

Page 37: ...1 1 1 1 Tridicator 75 160 psi 13 0305 1 1 1 1 1 1 1 46 Heat Exchanger Assembly Copper 70 2515 1R 1 Cast Iron prior to 0209 must replace 70 2516 1R 1 combustion chamber top panel 36 70 2517 1R 1 70 25...

Page 38: ...2 2 2 NS 10K Temperature Sensor 14 0325 3 3 3 3 3 3 3 50 Transformer 50 VA 15 0007 1 1 1 1 1 1 1 51 Purge Timer ST7800 16 0007 1 1 1 1 1 1 1 52 Spark Generator Q652B 16 0036 1 1 1 1 1 1 1 53 Flame Saf...

Page 39: ...0102 1 1 1 1 1 1 1 81 Pilot Orifice 052 NG 10 0140 1 1 1 1 1 1 1 Pilot Orifice 040 LP 10 0139 1 1 1 1 1 1 1 82 Mini Peeper C7027A 16 0009 1 1 1 1 1 1 1 83 Spark Plate Gasket 06 0102 1 1 1 06 0037 1 1...

Page 40: ...he electrical panel Disable any external call for heat and toggle the remote local switch to REMOTE 1 Toggle the LOW FIRE switch to cycle the boiler then hold at trial for pilot ignition 2 Set pressur...

Page 41: ...TWEEN THE HEATER INLET AND OUTLET IS CRITICAL TO PROPER FLOW BEFORE YOU LEAVE THE JOBSITE YOU MUST RECORD THE DELTA T THIS READING SHOULD NOT EXCEED 35 F 19 4 C NOR BE LOWER THAN 20 F 11 2 C DELTA T C...

Page 42: ...the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS g INSP...

Page 43: ...ubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty See Installation Instructions for proper pump performance Chemical corrosion no corrosive chemica...

Page 44: ...right 2014 Mestek Inc 260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782 www rbiwate...

Reviews: