Finned copper tube gas boilers & water heaters – Boiler Manual

2

  If the information in this manual is not followed  

exactly, a fire or explosion may result causing property, 

personal injury or loss of life.

Do not store or use gasoline or other flammable vapors 

and liquids in the vicinity of this or any other applianc
WHAT TO DO IF  YOU SMELL GAS:
•  Do not try to light any appliance.
•  Do  not  touch  any  electrical  switch.  Do  not  use  any 

phone in your building.

•   Immediately call your gas supplier from a neighbor’s 

phone. Follow the gas supplier’s instructions.

•   If  you  cannot  reach  your  gas  supplier,  call  the  fire 

department.

Installation and service must be performed by a qualified 

installer, service agency or the gas supplier.

  Assurez-vous de bien suivre les instructions données 

dans cette notice pour réduire au minimum le risque 

d’incendie ou d’explosion ou pour éviter tout dommoge 

matériel, toute blessure ou la mort

Ne  pas  entreposer  ni  utiliser  d’essence  ou  ni  d’autres  

vapeurs ou liquides inflammables à proximité de cet  

appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
•  Ne pas tenter d’allumer d’appareil. 
•  Ne touchez à aucun interrupteur; ne pas vous servir 

des téléphones se trouvant dans le bâtiment.

•   Appelez immédiatement votre fournisseur de gas depuis 

un voisin. Suivez les intructions du fournisseur. 

•   Si vous ne purvez rejoindre le fournisseur, appelez le 

service des incendies.

L’installation  et  l’entretien  doivent  être  assurés  par  un 

installateur  ou  un  service  d’entretien  qualifié  ou  par  le 

fournisseur de gaz.

  Failure to properly vent this unit can cause excessive 

amounts of carbon monoxide resulting in severe 

personal injury or death!

DESIGNED AND TESTED ACCORDING TO A.S.M.E. 

BOILER  AND  PRESSURE  VESSEL  CODE,  SECTION 

IV FOR A MAXIMUM ALLOWABLE WORKING PRES-

SURE OF 160 PSI, 1103 kPa WATER.

BEFORE YOU START     .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .   2
RATINGS & CAPACITIES    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  3
BOILER/WATER HEATER LOCATION  .  .  .  .  .  .  .  .  .  .  .  .  3
COMBUSTION AIR & VENTILATION  .  .  .  .  .  .  .  .  .  .  .  .  .  3

GENERAL VENTING GUIDELINES .  .  .  .  .  .  .  .  .  .  .  .  .  .  5
OUTDOOR VENTING .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 10
COMMON VENT SYSTEMS    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    . 11
GENERAL PIPING REQUIREMENTS   .  .  .  .  .  .  .  .  .  .  .  . 12

HEATING SYSTEM PIPING   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 13
DOMESTIC WATER SUPPLY PIPING    .    .    .    .    .    .    .    .    .    .    .    . 17

GAS SUPPLY PIPING   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 20

ELECTRICAL WIRING    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    . 21

GENERAL OPERATION   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 21
OPERATING INSTRUCTIONS    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    . 22
SEQUENCE OF OPERATION   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 24
CHECKING & ADJUSTMENTS .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 25

HEATNET FIELD WIRING   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 26
CONTROL DESCRIPTION  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 28
DIAGNOSTIC  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 28
MAINTENANCE   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 31

TROUBLE-SHOOTING   .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    . 33

REPAIR PARTS  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 34
START-UP SHEET   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 40
MASS CODE   .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    .    . 42
WARRANTY   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 43

BEFORE YOU START

 

This manual covers the application, installation, operation and 

maintenance of a Futera III Series finned copper heating boiler/

water heater/pool heater (Canada only). To obtain the safe, 

dependable, efficient operation and long life for which this heating 

boiler/water heater was designed, these instructions must be read, 

understood and followed.

The Futera III Series finned copper heating boiler/water heaters 

have been design certified by CSA for use with natural and propane 

gas under the latest revision of ANSI-Z21.10.3/CSA 4.3, Gas Water 

Heaters, ANSI-Z21.13/CSA 4.9, Gas-Fired Low Pressure Steam 

and Hot Water Boilers ANSI-Z21.56/CSA 4.7 Gas-Fired Pool 

Heaters (Canada only) and CAN1-3.1, Industrial and Commercial 

Gas Fired Packaged Boilers. Each unit has been constructed and 

hydrostatically tested for a maximum working pressure of 

160 psi

1103 kPa

 in accordance with Section IV of the A.S.M.E. Boiler 

and Pressure Vessel Code.

Summary of Contents for Futera II Modulation

Page 1: ...g construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The...

Page 2: ...it can cause excessive amounts of carbon monoxide resulting in severe personal injury or death DESIGNED AND TESTED ACCORDING TO A S M E BOILER AND PRESSURE VESSEL CODE SECTION IV FOR A MAXIMUM ALLOWAB...

Page 3: ...in mm Top 6 153 30 762 Back 6 153 24 610 Left Side 6 153 12 306 Right Side 6 153 12 306 Front 6 153 30 762 2 An optimum site will be level central to the piping system close to a chimney or outside w...

Page 4: ...within 12 in 305 mm of but not less than 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the bottom of the enclosure Where...

Page 5: ...sized to provide a negative draft of 03 in 0 8 mm to 1 in 2 5 mm W C at the flue outlet Common positive pressure vent systems are not to be used Improper installation can result in excessive levels of...

Page 6: ...The bottom of the vent terminal s shall be located at least 5 ft 1 5 m above the air intake terminal s unless there is a minimum 5 ft 1 5 m horizontal separation between them Avoid terminal locations...

Page 7: ...t and combustion air ter minals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds Incoldclimates double wallorinsulatedinletpipe recomme...

Page 8: ...s Boiler Manual 8 Figure 3 Vertical Air Intake and Venting for a Direct Vent System Category IV Figure 4 Combination Direct Vent Systems Category IV 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1...

Page 9: ...y into a listed metal chimney system Figures 7 9 Thechimneymustprovideanegativepressurenotgreaterthan0 10 in 2 5 mm W C at the boiler water heater flue collar with the unit running The Futera III when...

Page 10: ...at 3 ft 0 9 m intervals with overhead hangers Use a single wall stainless steel vent pipe the same diameter as the flue collar to connect the boiler water heater to a masonry chimney When using a list...

Page 11: ...e 9 Vertical Venting Using a Lined Masonry Chimney Category II Figure 11 Multiple Outdoor Units Figure 8 Vertical Venting Using a Lined Masonry Chimney Category I Figure 10 Outdoor Venting Category IV...

Page 12: ...nstall s et les autres espaces du b timent Mettre en marche les s cheuses tous les appareils non raccord s au syst me d vacuation commun et tous les ventilateurs d extraction comme les hottes de cuisi...

Page 13: ...pe of valve between the boiler waterheaterandthereliefvalveoranexplosioncausing extensive property damage severe personal injury or death may occur Flow Switch The flow switch supplied with the boiler...

Page 14: ...heater for proper wiring connections Expansion Tank Air Separator An expansion tank or other means to control thermal expansion must be installed in the heating system An expansion tank must be insta...

Page 15: ...urn temperature 7 For HeatNet operation a sensor is required and installed at a minimum of 12 from primary loop tee supplied Notice These drawings show suggested piping configuration and valving Check...

Page 16: ...rs furnished with factory mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplied 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow...

Page 17: ...nd by maintaining the pH between 5 and 9 Follow the conditions listed under NORMAL in the table In some areas of the country additional precautions must be observed due to unusual charac teristics of...

Page 18: ...Finned copper tube gas boilers water heaters Boiler Manual 18 Table 9 Futera III Heat Exchanger Selection Graph Table 10 Futera III Pumping Performance Requirement...

Page 19: ...ed pump max pipe length 30 ft total 6 90 elbows full pipe size 5 CAUTION MEASURE WATER HARDNESS AND pH AT JOB SITE 6 The pH and water hardness must be measured before selecting heat exchanger and pump...

Page 20: ...at the bottom of the vertical section of the gas supply pipe upstream of the gas controls A ground joint union should be installed between the boiler gas controls and the supply piping Each of these i...

Page 21: ...s installed oudoors The wire size must be compatible with the total amp draw of the circuit Refer to the wiring diagram supplied with the boiler water heater for proper wiring connections and boiler f...

Page 22: ...il a t plong dans l eau m me partiellement Faitesinspecterl appareilparuntecnicienqualifi et remplacez toute partie du syst me de contr le et toute com mande qui ont t plong s dans l eau Operating Ins...

Page 23: ...Nat Gas Category II and IV Firing rate 500 750 1000 1250 1500 1750 2000 Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc 100 2 2 4...

Page 24: ...off all electric power to the boiler if service is to be performed 3 Close the manual main and pilot gas shut off valves COMMENT COUPER L ADMISSION DE GAZ DE L APAREIL 1 R glez le thermostat la temp...

Page 25: ...when the boiler is firing at full rate Low gas pressure could indicate undersized gas line or insufficient gas supply Static and operating gas pressure required at the gas valve inlet is between 2 W...

Page 26: ...Finned copper tube gas boilers water heaters Boiler Manual 26 RBI FIELD WIRING TO HEATNET BOARD Figure 22 RBI Field Wiring to HeatNet Board Board Revision 3 0 and greater...

Page 27: ...n be used to control HeatNet equipped boilers Method 1 A 4 20mA signal can be used to directly modulate each boiler from a remote panel or building management system On multiple boiler installations t...

Page 28: ...y will also list faults should the unit fail to operate An explanation of each status message and fault can be located in HeatNet Control Manual under status screen fault display section STATUS SCREEN...

Page 29: ...ock is located on J11B SPARE 4 FAULT SYSTEM SET 160 F INTERLOCK SPARE 4 FLOW SWITCH ERROR Once the FIII series boiler receives a call for heat it closes the circulator pump relay It then waits 10 seco...

Page 30: ...ET 160 F OPEN OUTSIDE SENSOR SHORTED SENSOR If the shorted sensor fault is displayed thesensorinthepositionreportedwasoriginallydetected but has since shorted The boiler will shut down on any SHORTED...

Page 31: ...osits indicate condensation due to low return water temperatures In either case the heat exchanger must be cleaned thoroughly and the problem resolved before the boiler water heater is returned to ser...

Page 32: ...qualified service technician to have it inspected NEVER try to clean or repair the relief valve If the valve fails to operate properly have it replaced 5 Theaquastathighlimitcontrolsthemaximumwaterte...

Page 33: ...entify which interlock has tripped Reset the Interlock or check for disconnected wiring or shorts The Air Pressure from UV Sensor interlock if displayed will allow the boiler to function but it needs...

Page 34: ...Finned copper tube gas boilers water heaters Boiler Manual 34 Figure 25 Exploded View REPAIR PARTS...

Page 35: ...Finned copper tube gas boilers water heaters Boiler Manual 35 REPAIR PARTS CONTINUED RIOM 74 REV E...

Page 36: ...4 2 2 2 2 2 2 2 19 Flange 1 Outlet 11 0228 1 1 1 1 Flange 1 1 2 Outlet 11 0229 1 1 1 NS Orifice Gasket 06 0022 1 1 1 1 1 1 1 NS Gas Injectors NG 10 1009 1 1 1 1 Gas Injectors NG 10 1002 1 1 1 Gas Inje...

Page 37: ...1 1 1 1 Tridicator 75 160 psi 13 0305 1 1 1 1 1 1 1 46 Heat Exchanger Assembly Copper 70 2515 1R 1 Cast Iron prior to 0209 must replace 70 2516 1R 1 combustion chamber top panel 36 70 2517 1R 1 70 25...

Page 38: ...2 2 2 NS 10K Temperature Sensor 14 0325 3 3 3 3 3 3 3 50 Transformer 50 VA 15 0007 1 1 1 1 1 1 1 51 Purge Timer ST7800 16 0007 1 1 1 1 1 1 1 52 Spark Generator Q652B 16 0036 1 1 1 1 1 1 1 53 Flame Saf...

Page 39: ...0102 1 1 1 1 1 1 1 81 Pilot Orifice 052 NG 10 0140 1 1 1 1 1 1 1 Pilot Orifice 040 LP 10 0139 1 1 1 1 1 1 1 82 Mini Peeper C7027A 16 0009 1 1 1 1 1 1 1 83 Spark Plate Gasket 06 0102 1 1 1 06 0037 1 1...

Page 40: ...he electrical panel Disable any external call for heat and toggle the remote local switch to REMOTE 1 Toggle the LOW FIRE switch to cycle the boiler then hold at trial for pilot ignition 2 Set pressur...

Page 41: ...TWEEN THE HEATER INLET AND OUTLET IS CRITICAL TO PROPER FLOW BEFORE YOU LEAVE THE JOBSITE YOU MUST RECORD THE DELTA T THIS READING SHOULD NOT EXCEED 35 F 19 4 C NOR BE LOWER THAN 20 F 11 2 C DELTA T C...

Page 42: ...the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS g INSP...

Page 43: ...ubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty See Installation Instructions for proper pump performance Chemical corrosion no corrosive chemica...

Page 44: ...right 2014 Mestek Inc 260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782 www rbiwate...