RBI Futera II Modulation Installation And Operation Instructions Manual Download Page 21

Finned copper tube gas boilers & water heaters – Boiler Manual

21

  Never use an open flame to test for gas leaks. Always 

use an approved leak detection method. Failure to 

comply with this warning can cause extensive property 

damage, severe personal injury or death!

Whenever the gas supply piping is pressure tested the boiler/water 

heater gas controls must be protected. If the test pressure is equal 

to, or less than 

1/2 psig

3.5 kPa

 isolate the boiler/water heater 

by closing it’s manual shut off valve, see Figure 18. If the test pressure 

is greater than, or equal to 

1/2 psig

3.5 kPa

, disconnect the boiler/

water heater and its individual shut-off valve.

ELECTRICAL WIRING 

Electrical Power Connections

  Label all wires prior to disconnection when servicing 

controls. Wiring errors can cause improper and 

dangerous operation! Verify proper operation after 

servicing.

  Au moment de l’entretien des commandes, étiquetez 

tous les fils avant de les débrancher. Des erreurs de 

câblage peuvent entraîner un fonctionnement inadé-

quat et dangereux. S’assurer que l’appareil fonctionne 

adéquatement une fois l’entretirn terminé.

The electrical connections to this boiler/water heater must be made 

in accordance with all applicable local codes and the latest revision 

of the National Electrical Code, ANSI /NFPA-70. Installation should 

also conform with CSA C22.1 Canadian Electrical Code Part I if 

installed in Canada. 

Install a separate 120 volt 15 amp or 20 amp circuit breaker for the 

boiler/water heater and pump, see Table 13. A properly rated shut-

off switch should be located at the boiler/water heater. The boiler/

water heater must be grounded in accordance with the authority 

having jurisdiction, or if none, the latest revision of the National 

Electrical Code, ANSI/NFPA-70.

Table 13  Futera III Electrical Requirements

Recommended

Futera III

Circuit Breaker

*Running

Model

(Amps)

Amps

500

15

3.9

750 - 1000

15

6.0

1250 - 2000

20

11.4

*Use separate circuit breaker that is properly sized for pump and
pump contactor.

Line voltage field wiring of any controls or other devices must 

conform to the temperature limitation of type TEW wire at 

95°F

35°C

 above room temperature. Use copper conductors with a 

minimum size of #14 awg. Use appropriate wiring materials for 

units installed oudoors. The wire size must be compatible with the 

total amp draw of the circuit.  

Refer to the wiring diagram supplied with the boiler/water heater 

for proper wiring connections and boiler full load amperage (FLA).

GENERAL OPERATION

 

Before proceeding read and fully understand the  

instructions contained in this manual. Do not attempt 

to operate this boiler/water heater if it has not been 

installed in accordance with the guidelines set forth 

in this manual. Failure to comply with this warning 

can result in extensive property damage, severe per-

sonal injury or death!

Should overheating occur or the gas supply fail to shut off, turn off 

the manual gas control valve to the appliance.  Do not interrupt 

water flow through the boiler/water heater.
En cas de surchauffe ou si l’alimentation en gaz ne s’arrête pas, fermez 

manuellement le robinet d’arrêt de l’admission de gaz.

Hydronic Heating Boilers 

Open the make-up water valve and slowly fill the boiler and all of 

the radiation with water. Ensure that all bleed and drain valves are 

closed.

Adjust the make-up water pressure regulator so a minimum

12 psig

82.7 kPa

 system pressure is maintained at the highest point in the 

system piping. If a make-up water pump is used adjust it to maintain 

a minimum 

12 psig

82.7 kPa

 system pressure.

Open the system bleed and drain valves, one at a time, to purge 

the air trapped in the heating system piping.

With the boiler off, run the system pump for at least 30 minutes 

and bleed the system piping using the bleed valves. If strainers are 

used in the system piping, the make- up water valve should be closed 

and the strainers checked and cleaned.

The system expansion tank should be checked to ensure that the 

correct water level in the tank is maintained. The tank should be 

less than half full of water with the system full and adjusted to the 

correct operating pressure.
Start the boiler as described in the “OPERATING INSTRUCTIONS” 

section. Run the boiler for at least an hour.  The system pump(s) 

and all radiation units must be operated during this time. Ensure 

that the make-up water valve is open.
Shut the boiler off and open the bleed valves to purge the air trapped 

in the heating system piping. Close the make-up water valve and 

check and clean the strainers and make-up water pressure reducing 

valve.
Open the make-up water valve and adjust the system pressure if 

necessary. The system should be checked and bled after three days 

of operation.

Summary of Contents for Futera II Modulation

Page 1: ...g construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The...

Page 2: ...it can cause excessive amounts of carbon monoxide resulting in severe personal injury or death DESIGNED AND TESTED ACCORDING TO A S M E BOILER AND PRESSURE VESSEL CODE SECTION IV FOR A MAXIMUM ALLOWAB...

Page 3: ...in mm Top 6 153 30 762 Back 6 153 24 610 Left Side 6 153 12 306 Right Side 6 153 12 306 Front 6 153 30 762 2 An optimum site will be level central to the piping system close to a chimney or outside w...

Page 4: ...within 12 in 305 mm of but not less than 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the bottom of the enclosure Where...

Page 5: ...sized to provide a negative draft of 03 in 0 8 mm to 1 in 2 5 mm W C at the flue outlet Common positive pressure vent systems are not to be used Improper installation can result in excessive levels of...

Page 6: ...The bottom of the vent terminal s shall be located at least 5 ft 1 5 m above the air intake terminal s unless there is a minimum 5 ft 1 5 m horizontal separation between them Avoid terminal locations...

Page 7: ...t and combustion air ter minals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds Incoldclimates double wallorinsulatedinletpipe recomme...

Page 8: ...s Boiler Manual 8 Figure 3 Vertical Air Intake and Venting for a Direct Vent System Category IV Figure 4 Combination Direct Vent Systems Category IV 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1...

Page 9: ...y into a listed metal chimney system Figures 7 9 Thechimneymustprovideanegativepressurenotgreaterthan0 10 in 2 5 mm W C at the boiler water heater flue collar with the unit running The Futera III when...

Page 10: ...at 3 ft 0 9 m intervals with overhead hangers Use a single wall stainless steel vent pipe the same diameter as the flue collar to connect the boiler water heater to a masonry chimney When using a list...

Page 11: ...e 9 Vertical Venting Using a Lined Masonry Chimney Category II Figure 11 Multiple Outdoor Units Figure 8 Vertical Venting Using a Lined Masonry Chimney Category I Figure 10 Outdoor Venting Category IV...

Page 12: ...nstall s et les autres espaces du b timent Mettre en marche les s cheuses tous les appareils non raccord s au syst me d vacuation commun et tous les ventilateurs d extraction comme les hottes de cuisi...

Page 13: ...pe of valve between the boiler waterheaterandthereliefvalveoranexplosioncausing extensive property damage severe personal injury or death may occur Flow Switch The flow switch supplied with the boiler...

Page 14: ...heater for proper wiring connections Expansion Tank Air Separator An expansion tank or other means to control thermal expansion must be installed in the heating system An expansion tank must be insta...

Page 15: ...urn temperature 7 For HeatNet operation a sensor is required and installed at a minimum of 12 from primary loop tee supplied Notice These drawings show suggested piping configuration and valving Check...

Page 16: ...rs furnished with factory mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplied 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow...

Page 17: ...nd by maintaining the pH between 5 and 9 Follow the conditions listed under NORMAL in the table In some areas of the country additional precautions must be observed due to unusual charac teristics of...

Page 18: ...Finned copper tube gas boilers water heaters Boiler Manual 18 Table 9 Futera III Heat Exchanger Selection Graph Table 10 Futera III Pumping Performance Requirement...

Page 19: ...ed pump max pipe length 30 ft total 6 90 elbows full pipe size 5 CAUTION MEASURE WATER HARDNESS AND pH AT JOB SITE 6 The pH and water hardness must be measured before selecting heat exchanger and pump...

Page 20: ...at the bottom of the vertical section of the gas supply pipe upstream of the gas controls A ground joint union should be installed between the boiler gas controls and the supply piping Each of these i...

Page 21: ...s installed oudoors The wire size must be compatible with the total amp draw of the circuit Refer to the wiring diagram supplied with the boiler water heater for proper wiring connections and boiler f...

Page 22: ...il a t plong dans l eau m me partiellement Faitesinspecterl appareilparuntecnicienqualifi et remplacez toute partie du syst me de contr le et toute com mande qui ont t plong s dans l eau Operating Ins...

Page 23: ...Nat Gas Category II and IV Firing rate 500 750 1000 1250 1500 1750 2000 Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc Signal Inches wc 100 2 2 4...

Page 24: ...off all electric power to the boiler if service is to be performed 3 Close the manual main and pilot gas shut off valves COMMENT COUPER L ADMISSION DE GAZ DE L APAREIL 1 R glez le thermostat la temp...

Page 25: ...when the boiler is firing at full rate Low gas pressure could indicate undersized gas line or insufficient gas supply Static and operating gas pressure required at the gas valve inlet is between 2 W...

Page 26: ...Finned copper tube gas boilers water heaters Boiler Manual 26 RBI FIELD WIRING TO HEATNET BOARD Figure 22 RBI Field Wiring to HeatNet Board Board Revision 3 0 and greater...

Page 27: ...n be used to control HeatNet equipped boilers Method 1 A 4 20mA signal can be used to directly modulate each boiler from a remote panel or building management system On multiple boiler installations t...

Page 28: ...y will also list faults should the unit fail to operate An explanation of each status message and fault can be located in HeatNet Control Manual under status screen fault display section STATUS SCREEN...

Page 29: ...ock is located on J11B SPARE 4 FAULT SYSTEM SET 160 F INTERLOCK SPARE 4 FLOW SWITCH ERROR Once the FIII series boiler receives a call for heat it closes the circulator pump relay It then waits 10 seco...

Page 30: ...ET 160 F OPEN OUTSIDE SENSOR SHORTED SENSOR If the shorted sensor fault is displayed thesensorinthepositionreportedwasoriginallydetected but has since shorted The boiler will shut down on any SHORTED...

Page 31: ...osits indicate condensation due to low return water temperatures In either case the heat exchanger must be cleaned thoroughly and the problem resolved before the boiler water heater is returned to ser...

Page 32: ...qualified service technician to have it inspected NEVER try to clean or repair the relief valve If the valve fails to operate properly have it replaced 5 Theaquastathighlimitcontrolsthemaximumwaterte...

Page 33: ...entify which interlock has tripped Reset the Interlock or check for disconnected wiring or shorts The Air Pressure from UV Sensor interlock if displayed will allow the boiler to function but it needs...

Page 34: ...Finned copper tube gas boilers water heaters Boiler Manual 34 Figure 25 Exploded View REPAIR PARTS...

Page 35: ...Finned copper tube gas boilers water heaters Boiler Manual 35 REPAIR PARTS CONTINUED RIOM 74 REV E...

Page 36: ...4 2 2 2 2 2 2 2 19 Flange 1 Outlet 11 0228 1 1 1 1 Flange 1 1 2 Outlet 11 0229 1 1 1 NS Orifice Gasket 06 0022 1 1 1 1 1 1 1 NS Gas Injectors NG 10 1009 1 1 1 1 Gas Injectors NG 10 1002 1 1 1 Gas Inje...

Page 37: ...1 1 1 1 Tridicator 75 160 psi 13 0305 1 1 1 1 1 1 1 46 Heat Exchanger Assembly Copper 70 2515 1R 1 Cast Iron prior to 0209 must replace 70 2516 1R 1 combustion chamber top panel 36 70 2517 1R 1 70 25...

Page 38: ...2 2 2 NS 10K Temperature Sensor 14 0325 3 3 3 3 3 3 3 50 Transformer 50 VA 15 0007 1 1 1 1 1 1 1 51 Purge Timer ST7800 16 0007 1 1 1 1 1 1 1 52 Spark Generator Q652B 16 0036 1 1 1 1 1 1 1 53 Flame Saf...

Page 39: ...0102 1 1 1 1 1 1 1 81 Pilot Orifice 052 NG 10 0140 1 1 1 1 1 1 1 Pilot Orifice 040 LP 10 0139 1 1 1 1 1 1 1 82 Mini Peeper C7027A 16 0009 1 1 1 1 1 1 1 83 Spark Plate Gasket 06 0102 1 1 1 06 0037 1 1...

Page 40: ...he electrical panel Disable any external call for heat and toggle the remote local switch to REMOTE 1 Toggle the LOW FIRE switch to cycle the boiler then hold at trial for pilot ignition 2 Set pressur...

Page 41: ...TWEEN THE HEATER INLET AND OUTLET IS CRITICAL TO PROPER FLOW BEFORE YOU LEAVE THE JOBSITE YOU MUST RECORD THE DELTA T THIS READING SHOULD NOT EXCEED 35 F 19 4 C NOR BE LOWER THAN 20 F 11 2 C DELTA T C...

Page 42: ...the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS g INSP...

Page 43: ...ubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty See Installation Instructions for proper pump performance Chemical corrosion no corrosive chemica...

Page 44: ...right 2014 Mestek Inc 260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782 www rbiwate...

Reviews: