66
Technical Data
VERSA IC
®
Control Board Ratings
PIM™ Ratings
Enclosure
Bare board with stand-offs
Power Supply
24 VAC +/- 10%, 60Hz
Control Load
TBD
Safety/Fan/Extra Relays 240VAC, 5A
Modulating Output
0-10 VDC, 3K min. load impedance / 0-20mA
Demands
Connect to 24VAC return to initiate demand
Ambient Conditions
Inside enclosure use ONLY; 32°F to 122°F (0°C to 60°C), <90% relative humidity
non-condensing
Input Power
18-30 VAC 50/60Hz (Class 2 transformer)
Input Current Drain
400mA @ 24VAC with gas and blower relays energized
Gas Valve Relays
5.0A max (continuous)
Combustion Blower
5.0A max for standard (J2) connection
15.0A max for heavy duty (K5 relay) terminals
Hot Surface Igniter
5.0A max, 120/240VAC
Pump Relays
5.0A max (continuous)
Alarm Relay
2.0A, 30VDC or 30VAC max
Operating Temperature
-40 to +176°F (-40 to +80°C)
Storage Temperature
-40 to +185°F (-40 to +85°C)
Flame Sensitivity
0.7 µA minimum
Flame Failure Response or
Reignition Time
0.8 seconds minimum
Flame Detector Self-Check
Rate
Once per second minimum
Flame Failure Lockout Time
Varies by model
Spark Rate
Remote sense – 50/60Hz; Local sense – 25/30Hz
Moisture Resistance
Conformal coated to operate non-condensing to 95% relative humidity